5.10

Combustion head adjustment

The adjustment of the combustion head depends only on the
maximum output of the burner.
Turn the screw 5)(Fig. 21) until the notch indicated in diagram
(Fig. 22) corresponds with the front part of the flange 6)(Fig. 21).
To facilitate the adjustment, loosen the screw
1)(Fig. 17), adjust, then block.
ATTENTION
Example: Burner RLS 160/M MX
Burner maximum output = 1500 kW.
The diagram (Fig. 22) shows that for this output, the adjustment
of the combustion head is carried out on notch 7.
Installation
No. of holes
21
GB
D1149
Max burner output - kW
Fig. 21
D2996
Fig. 22
20148049