Calibration of the thermal relay

The thermal relay (Fig. 10) serves to avoid damage to the motor
due to an excessive absorption increase or if a phase is missing.
For calibration 2), refer to the table indicated in the electrical
layout (electrical wiring by the installer).
To reset, in case of thermal relay activation, press the "RESET"
button 1). The button "STOP" 3) opens the NC contact (95-96)
and stops the motor. Insert a screwdriver in the window "TEST/
TRIP" 4) and move it in the arrow direction (to the right) to carry
out the thermal relay test.
The automatic reset can be dangerous.
This operation is not foreseen in the burner
operation.
ATTENTION
4.17

Motor rotation

As soon as the burner starts, place yourself in front of the cooling
fan of the fan motor and check that it turns anticlockwise
(Fig. 11).
If this is not the case:
 put the switch of the burner to "0" (off) and wait until the
control box carries out the switching off phase.
Disconnect the electrical supply from the burner
by means of the system main switch.
DANGER
 Invert the phases on the three-phase motor power supply.
Technical description of the burner
15
GB
T O
I P
A U
/ T R
S T
N
M A
O P
T E
S T
T
S E
N C
R E
9 5
9 6
N O
9 7
9 8
D8685
4
2
1
20162359
3
Fig. 10
Fig. 11
20148049

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

20147789201477902014788720147888781t

Table of Contents