Flame Presence Check; Safety Components - Riello RLS 160/M MX Installation, Use And Maintenance Instructions

Dual fuel light oil/ gas burners progressive two-stage or modulating operation gas side/two-stage light oil side
Table of Contents

Advertisement

Fan
Check to make sure that no dust has accumulated inside the fan
or on its impellers, as this condition will cause a reduction in the
air flow rate and provoke polluting combustion.
Servomotor
Release cam 4)(Fig. 38 on page 32) from the servomotor, by
pressing and shifting button 3)(Fig. 39 on page 33) to the right.
Manually rotate it backwards and forwards to make sure it moves
smoothly. Now engage the cam again by shifting the button
2)(Fig. 39 on page 33) to the left.
Boiler
Clean the boiler as indicated in its accompanying instructions in
order to maintain all the original combustion characteristics
intact, especially: the flue gas temperature and combustion
chamber pressure.
Flame inspection window
Clean the glass of the flame inspection window (Fig. 45).
D484
7.2.4

Flame presence check

Check the level of the flame detection signal with the "Check
Mode" function from the flame control: LEDs from 2 to 6 indicate
the flame signal level, respectively.
See "LED indicator and special function" on page 41.
Check Mode
With burner flame on:
 hold the reset button on the flame control pressed for at
least 3 sec.;
 the button colour will change from green to yellow;
 each operating status signalling LED will be compared to
20% of the maximum brightness;
 press the reset button again (<0.5sec) to reset the standard
operation of the signalling LEDs.
20148049
Maintenance
7.2.5

Safety components

The safety components must be replaced at the end of their life
cycle indicated in Tab. N.
The specified life cycles do not refer to the warranty terms
indicated in the delivery or payment conditions.
Safety component
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor (electronic
cam) (if present)
Oil valve (solenoid)(if
present)
Oil regulator (if present)
Oil pipes/ couplings
(metallic) (if present)
Flexible hoses (if present)
Fan impeller
Fig. 45
38
GB
Life cycle
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
15 years
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years
5 years or 30.000 pressurised
cycles
10 years or 500.000 start-ups
Tab. N

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

20147789201477902014788720147888781t

Table of Contents