TECHNICIAN SETUP MENU

1. Press MENU button.
2. Press and hold TECH SET button for 3 seconds.
3. Configure the installer options as desired using the table below.
4. Use the + OR - keys to change settings and the NEXT STEP or PREV STEP
key to move from one option to another.
Note: Only press DONE key when you want to exit the Technician Setup Options.
Filter Change
Feature
Reminder
You can adjust
the filter change
reminder from
Adjustment
OFF to 2000
Options
hours of runtime
in 50 hour
increments.
8
Room
Minimum
Temperature
Compressor On
Calibration
Time
You can select
You can adjust
the minimum
the room
compressor run time
temperature
from OFF, 3, 4, or 5
display to read
minutes, if 3, 4, or
- 4°F to 4°F
5 is selected, the
above or below
compressor will run
the factory
for at least the
calibrated
selected time before
reading.
turning off.
Compressor
Cooling
Short Cycle
Differential or
Swing
Delay
The cooling
differential
(also called
swing) setting is
Selecting ON
adjustable from ±
will not allow
0.2°F to ±2°F.
the compressor
For example:
to be turned on
A differential
for 5 minutes
setting of 0.5°F
after the last
will turn the
time the
cooling on at
compressor
approximately
was on. Select
0.5°F above the
OFF to remove
setpoint and turn
this delay.
the cooling off at
approximately
0.5°F below the
setpoint.
Heating
Differential or
Swing
The heating
differential
(also called
swing) setting is
adjustable from
±0.2°F to ±2°F
For example: A
differential
setting of 0.5°F
will turn the
heating on at
approximately
0.5°F below the
setpoint and turn
the heating off
at approximately
0.5°F above the
setpoint.