LG Multi V ARWM072CAS5 Service Manual page 58

Outdoor unit r410a
Hide thumbs Also See for Multi V ARWM072CAS5:
Table of Contents

Advertisement

HR Unit PCB
2) Selection of the model of the HR unit
(For 2 branches) PRHR022A
Initial
Setting
1 branches
Connected
2 branches
Connected
3 branches
Connected
4 branches
Connected
h Each model is shipped with the switches No.2 and No.3 pre-adjusted as above in the factory.
WARNING
• If you want to use a PRHR022A for 2 branches HR unit after closing the 3rd pipes, set the dip switch for 2 branches HR unit.
• If you want to use a PRHR032A for 3 branches HR unit after closing the 4th pipes, set the dip switch for 3 branches HR unit.
• If you want to use a PRHR042A for 2 branches HR unit after closing the 3rd and 4th pipes, set the dip switch for 2 branches HR unit.
• The unused port must be closed with a copper cap, not with a plastic cap.
2
1
(For 3 branches) PRHR032A
- 58 -
3
2
1
(For 4 branches) PRHR042A
Copyright © 2020 LG Electronics. Inc.
All right reserved. Only for training and service purposes
3 4
1 2

Advertisement

Table of Contents
loading

Table of Contents