ARW = MULTI V Water V Water Source Unit (Refrigerant R410A) Type To reduce the risk of designing an improper applied system or one that will not operate correctly, LG requires that LATS software be used on all M = Inverter Heat Pump & Heat Recovery projects.
Chassis I.D. Size Quantity CF (Ref.) Total (lbs.) size, and by pipe segments. LATS can generate an Excel GERP report that can imported into the LG SOPS pricing and ordering system. Linear feet of 1/4" liquid line tubing — — 0.015 Linear feet of 3/8"...
(variable from 20 to 140Hz. The compressor has a built-in oil levels as low as 47 dB(A) in cooling mode and 51 dB(A) in heating mode. LG customers often ask if the water source unit is running after level sensor to provide real-time oil control.
– – LG MULTI V Water V simplify and reduce the mechanical and control system design time. The designer no longer has to be concerned with Cooling Performance interconnecting chilled and condenser water piping, air-distribution duct systems, matching and selecting chillers, towers, pumps, coils, fans,...
Page 8
Value is calculated as follows: Δt = Total Heat of Rejection/(Nominal Flow Rate x 500). LG requires that LATS software be used on all projects to ensure correct line sizing. Designer must verify the shop drawing design drawing design against the as built design using LATS. Contractor must also use LG manufactured Y-Branch and Header...
ELECTRICAL CONNECTIONS System for Heat Pump Configuration on page 42 System for Heat Recovery Configuration on page 43 DIP Switch Settings For Use With Gen 4 Indoor Units on page 44...
Page 24
Generation 4 Equipment The latest versions of LG s indoor units are designated Generation 4 (Gen 4). or Gen 4 indoor units to operate with Gen 4 indoor unit fea- tures, the air conditioning system must meet the following requirements: •...
575V Performance Data Manual for performance at different entering water temperatures. When entering water temperature is below 59°F, the LG variable water flow control kit Model No. PWFCKN000 is required. At the high end of this temperature range, a heat rejecter (cooling tower, dry cooler, geothermal well) is required to remove heat, while at the low end of the temperature range, an auxiliary heat source (boiler, solar panel, geothermal well) must add heat.
Page 29
Solenoid Valves (Optional) When entering water temperature is lower than 59ºF, variable water flow control kit PWFCKN000 is required. LG recommends installing a Solenoid valves may be installed to shut off water flow to the water source unit when the unit turns off. Solenoid valves are field supplied, must be rated for 208-230V, and must be wired to terminals L1 and L2 on the water source unit PCB as shown in the following figure.
Page 30
Variable Water Flow Valve Control Kit for Dual Frame LG recommends installing a variable water flow valve control kit on each water source unit. Refer to the figures on the following pages for Figure 22: Variable Water Flow Valve Control Kits for Dual Frame single, dual, and triple frame configurations.
PIPING LIMITATIONS For Systems Designed for Heat Pump Configuration Following pages present Multi V Water V piping limitations and are for illustrative purposes only. Designers MUST use LATS when designing LG VRF systems. Figure 25: Typical Heat Pump System Building Layout with Piping Limitations.
For Systems Designed for Heat Pump Operation Following pages present Multi V Water V piping limitations and are for illustrative purposes only. Designers MUST use LATS when designing LG VRF Following pages present Multi V Water V piping limitations and are for illustrative purposes only. Designers MUST use LATS when designing LG VRF Following pages present Multi V 5 piping limitations and are for illustrative purposes only.
Page 34
The piping MUST be Following pages present Multi V Water V piping limitations and are for illustrative purposes only. Designers MUST use LATS when designing LG VRF Heat Pump Outdoor Unit Service Port Diagram.
Page 35
For Systems Designed for Heat Recovery Configuration Following pages present Multi V Water V piping limitations and are for illustrative purposes only. Designers MUST use LATS when designing LG VRF Following pages present Multi V Water V piping limitations and are for illustrative purposes only. Designers MUST use LATS when designing LG VRF systems.
Page 36
For Systems Designed for Heat Recovery Configuration Following pages present Multi V Water V piping limitations and are for illustrative purposes only. Designers MUST use LATS when designing LG VRF Following pages present Multi V Water V piping limitations and are for illustrative purposes only. Designers MUST use LATS when designing LG VRF systems.
Multi V Water 5 Piping and Service Ports Piping Selection Following pages present Multi V Water V piping limitations and are for illustrative purposes only. Designers MUST use LATS when designing LG VRF LG Multi V Water 5 systems can be configured to operate as either systems.
Page 41