LG Multi V ARWM072CAS5 Service Manual page 156

Outdoor unit r410a
Hide thumbs Also See for Multi V ARWM072CAS5:
Table of Contents

Advertisement

Self-diagnosis function
Error No.
Error Type
Communication error
between Master and
207C#HR
Slave Main PCB of HR
Unit
n Error diagnosis and countermeasure flow chart
1) Check if DIP switch No.5 of SW02E on Slave Main PCB is ON.
2) Check the communication connection between Master and Slave Main PCB of HR Unit even after check No.1
process.
3) Replace Main PCB of HR Unit even after check No.2 process.
Error No.
Error Type
Communication error of
208C#HR
EEPROM of HR Unit
n Error diagnosis and countermeasure flow chart
1) Check the wiring connection between EEPROM and Main PCB of HR Unit.
2) Replace Main PCB of HR Unit even after check No.1 process.
Error Point
When fail to communication
between Master and Slave
Main PCB of HR Unit
Error Point
When fail to communication
of EEPROM of HR Unit
- 156 -
Main Reasons
1. Wiring defect between Main and Slave Main
PCB of HR Unit.
2. Defect of the Main PCB of HR Unit.
Main Reasons
1. Wiring defect between EEPROM and Main
PCB of HR Unit.
2. Wiring wrong type of EEPROM.
3. Defect of the Main PCB of HR Unit.
Copyright © 2020 LG Electronics. Inc.
All right reserved. Only for training and service purposes

Advertisement

Table of Contents
loading

Table of Contents