3.2 Discharge temperature control

• Outdoor unit control
Temperature range
Tdis > 113 ℃(235.4 ℉)
Tdis > 110 ℃(230 ℉)
Tdis ≥ 105 ℃(221 ℉)
Tdis ≥ 100 ℃(212 ℉)
Tdis < 100 ℃(212 ℉)
SC : Sub Cooling, SH : Super Heating

3.3 Inverter protection control

AC Input Current
Compressor Current
h AC input current is input current of inverter compressor except constant current (current pass through noise filter)
Compressor
-5 Hz/10 Second
-5 Hz/30 Second
Frequency holding
+3 Hz or less
Normal control
Compressor(kW)
Normal Operation
17
17
- 24 -
Sub cooling EEV
SC,SH decrease control
SC,SH decrease control
SC,SH decrease control
SC,SH decrease control
SC,SH decrease control
Cooling & Heating
Frequency Down
25 A or less
25 A or more
29 A or less
29 A or more
Copyright © 2020 LG Electronics. Inc.
All right reserved. Only for training and service purposes
IDU EEV
SH decrease control
SH decrease control
SH decrease control
SH decrease control
SH decrease control
System Stop
27 A or more
40 A or more