Cycle Data View - LG Multi V ARWM072CAS5 Service Manual

Outdoor unit r410a
Hide thumbs Also See for Multi V ARWM072CAS5:
Table of Contents

Advertisement

Function

4.13 Cycle Data View

This function is intended to identify the Cycle data of Outdoor unit, which is running on.
The 7 Segment is display 16 different cycle data.
Cycle data view function setting method
step
op1
Current High Pressure
op2
Current low Pressure
op3
Inv 1 Pulse
op6
Superheating degree
op7
Subcooling degree
op8
ODU temp.
op9
Suction temp.
op10
Comp1 discharge temp.
op12
Liquid pipe temp.
op14
Sc_out
op15
Water out temp.
op16
Water in temp.
op17
Hc_out
op18
Inlet pipe temp of IDU
op19
main1 eev
op21
sc eev
op22
hc eev
op25
IDU running capacity
op26
Total number of IDU
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button : "SVC"
Push the '●' button
Select the Function using '▶', '◀' Button : "SE8"
Push the '●' button
Selec the Option using '▶', '◀' Button :
"op1~op16" Push the '●' button
Start the Cyce data view fuction : Display the
cycle data value selected from the Segment.
Title
7-seg
P1
P2
h1
T1
T2
T3
T4
T5
T7
T9
T10
T11
T12
T13
PLS1
PLS3
PLS4
IDU1
IDU2
example
seg_1
4321 kPa
4
1234 kPa
1
120 Hz
5.3 ℃
-4.5 ℃
10 ℃
43.4 ℃
150 ℃
10 ℃
10 ℃
10 ℃
10 ℃
10 ℃
-10 ℃
-
1940 pls
1
16 pls
50 pls
24 kBtu
10 EA
- 42 -
Copyright © 2020 LG Electronics. Inc.
All right reserved. Only for training and service purposes
seg_2
seg_3
seg_4
3
2
1
2
3
4
1
2
0
5
3
-
4
5
1
0
0
4
3
4
1
5
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
9
4
0
1
6
5
0
2
4
1
0

Advertisement

Table of Contents
loading

Table of Contents