* Measure the resistance of 4way valve
** Confirm the 4way valve coil is inserted to the end
*** When power is supplied in order as follow
(Slave2 ' Slave1 ' Mater)
ODU information is displayed one after the other at main PCB 7-segment
1. Model ID
' 8 HP : 8, 10 HP : 10, 12 HP : 12, 14 HP : 14, 16 HP : 16, 18 HP : 18, 20 HP : 20
2. Total Capacity
' Displayed with HP
3. ODU Type
' Heat Pump : 2
' Heat Recovery : 3
4. Power type
' 575 V : 57
5. Model type
' CAS5 : 30
***** Checking method for outdoor unit of 3unit system
(Master + Slave1 + Slave2)
¿ Close all the SVC valves of high / low pressure
¡ Operate system
¬ Check the difference of high and low pressure with LGMV for each unit (Master, Slave1, Slave2)
√ If there is a unit in which the difference is not increased then the 4way valve of that unit is defective
Location of 4way valve connector on
Main PCB(marked as 4way,CN09)
**** Check the output voltage of terminal socket
during heating operation
- 145 -
Copyright © 2020 LG Electronics. Inc.
All right reserved. Only for training and service purposes