n Example. Slave2 ODU inverter compressor failure (For Heat Recovery System)
Close
Open
Heating mode
Slave2
Liquid
Low
High
Pipe
pressure
Pressure
Gas Pipe
Gas Pipe
1. Close liquid pipe and low pressure gas pipe of the unit for pump out operation.
2. Operate pump out
3. Close high pressure gas pipe of unit after completion
4. End pump out
5. After replacing the compressor, eliminate remaining refrigerant of corresponding ODU and perform vacuum
work. (with vacuum mode)
6. Add the refrigerant with auto charging function
Heating mode
Slave1
Liquid
Low
High
Pipe
pressure
Pressure
Gas Pipe
Gas Pipe
Liquid pipe
Low Pressure Gas pipe
High Pressure Gas pipe