Protection Control; Pressure Protection Control - LG Multi V ARWM072CAS5 Service Manual

Outdoor unit r410a
Hide thumbs Also See for Multi V ARWM072CAS5:
Table of Contents

Advertisement

3. Protection control

3.1 Pressure protection control

3.1.1 Pressure control on cooling mode
• High pressure control
Pressure Range
P
≥ 4000 kPa(580.2 psi)
d
P
> 3775 kPa(547.5 psi)
d
P
≥ 3650 kPa(529.4 psi)
d
P
≥ 3480 kPa(504.7 psi)
d
P
< 3480 kPa(504.7 psi)
d
• Low pressure control
Pressure Range
P
≤ 110 kPa(16 psi) 1 minute later operation
s
P
≤ 150 kPa(21.8 psi) 1 minute before operation
s
h Frequency holding : frequency (or RPM) is not increasing (can decrease)
3.1.2 Pressure control on heating mode
• High pressure control
Pressure Range
P
≥ 4000 kPa(580.2 psi)
d
P
> 3415 kPa(495.3 psi)
d
• Low pressure control
Pressure Range
739 kPa(107.2 psi) < P
P
≤ 739 kPa(107.2 psi)
s
h Frequency holding : frequency (or RPM) is not increasing (can decrease).
≤ 778 kPa(112.8 psi)
s
-15Hz/10Second
Frequency holding
+2 Hz or less/10Second
Normal control
-10Hz/10Second
-15Hz/10Second
Frequency holding
- 23 -
Copyright © 2020 LG Electronics. Inc.
All right reserved. Only for training and service purposes
Function
Compressor
Stop
Compressor
Stop
Compressor
Stop
Compressor
-5Hz/7sec.