Specifications

Input Characteristics

Filter Characteristics

1
The SCC-AIXX does not provide isolation between the two channels of the module. For more information,
refer to the
Connecting the Input Signals
2
This specification is calculated relative to the input range of the module.
© National Instruments Corporation
These ratings are typical at 25 °C unless otherwise stated.
Number of input channels ...................... 2 NRSE
Isolation.................................................. Bank isolation (isolation
Input/output signal range, gain,
and bandwidth ........................................ Refer to Table 1-1
Input impedance
SCC-AI01, SCC-AI02 .................... 1 MΩ
All others......................................... 100 MΩ
Gain error ............................................... 4.5% max (trimmable to zero)
Gain stability .......................................... 150 PPM/°C
Offset error ............................................. 40 mV max (RTI
Offset stability........................................ 225 µV/°C
Nonlinearity ........................................... 0.0128% typ
Common-mode rejection ratio ............... 100 dB typical at 60 Hz
Output slew rate,
dependent on BW (filtering) .................. 0.8 V/µs max
Number of poles..................................... 3
Rolloff .................................................... 60 dB/decade
Cutoff frequency (–3 dB)
AI0X................................................ 10 kHz
AI1X................................................ 4 Hz
section.
per module)
0.0260% max
9