Can I assign different modes (ON/OFF, only OFF, ON/corr) to different motion sensors?
• No� All presence detectors/motion sensors connected to the PD/T input and the universal, digital Contr�IN inter-
face use the same mode that has been set for the DIMLITE control device�
The ED-SENS multi-sensor is not responding What may be causing this?
• The on/off key of the IRTOUCH remote control may have accidentally been pressed when the ED-SENS multi-
sensor was being assigned, causing its assignment to be invalidated�
• Check that the desired mode is set for the presence-linked control on the DIMLITE control device�
Why does the system switch on automatically several minutes after the lighting has been manually
switched off?
• Check whether presence-linked control MODE ON/corr is set� With this presence-linked control mode, the cor-
ridor lighting scene (all luminaire groups set to 10% brightness) is recalled if no one is present in the detection
range of the presence detector and once the run-on time and fade time have expired (64 s)� This will also occur
if the lighting has been switched off manually and no motion sensor or ED-SENS multi-sensors are connected
to the DIMLITE control device� If presence-linked control is set to MODE ON/corr the lighting cannot be perma-
nently switched off�
Why does the system switch off automatically several minutes after the lighting has been manually
switched on, even though no presence detectors/motion sensors are connected?
• Presence-linked control is enabled� If no presence-linked control is desired, set the mode rotary selector
switch on the DIMLITE control device to "no funct�"�
What happens if I connect too many devices to the universal, digital ContrIN interface
• It is no longer possible to guarantee that the DIMLITE system will function correctly because the Contr�IN inter-
face is overloaded� Reduce the number of devices (ED-Cxx, ED-SxED, ED-SENS, ED-EYE, ED-IR) to 8 units� The
status LED glows permanently red when there is an overload on the universal, digital Contr�IN interface�
Can one dimming rocker key on the CIRCLE ED-Cxx control unit be used to dim all luminaire groups
simultaneously?
• No�
Can multiple DIMLITE control devices be networked?
• No�
What do I have to reconfigure when replacing a DIMLITE control device?
• See the section "Replacing the DIMLITE control device", page 38�
Are the current user settings saved if the power is interrupted?
• Yes� When the voltage suppy is restored, the lighting scene that was active before the voltage supply was in-
terrupted is recalled�