Table of Contents

Advertisement

2� Switch the lighting off or recall lighting scene 2 or 3�
This will provide a stable starting point for setting the system points�
3� Place a luxmeter on the workspace (e�g� desk) located underneath the desired luminaire group�
4� Smoothly adjust each luminaire group until the required illuminance has been achieved on each workspace
according to the reading on the luxmeter�
5� Wait approx� 30 seconds once the illuminance has been set� Check whether the illuminance has remained
constant according to the reading on the luxmeter� If the illuminance has changed, smoothly adjust each
luminaire group until the required illuminance has been achieved once again� Repeat this step until the
illuminance remains constant�
6� Save the day points or twilight points (see the section "Saving system points", page 34)�
7� Recall lighting scene 1� Check whether the illuminance reaches the desired value� If the illuminance does not
match, repeat the process from step 4 onwards�
8� If the mode rotary selector switch has first been set to "no funct�": reset the mode rotary selector switch on
the DIMLITE control device to the previous rotary selector switch position�
Note:
! Note that you cannot save a system point for an individual luminaire group� Saving applies the current settings
to all luminaire groups�
Saving system points
The following devices can be used to save system points:
Device
CIRCLE control unit ED-Cxx
ED-EYE light sensor
D-SxED input device
(rotary selector switch
position 1)
IRTOUCH remote control
DIMLITE control device
Example: ED-Cxx
7 s – 12 s
34 DIMLITE Installation and commissioning manual 4.0 | 01.2014 | en
Key/momentary-action
switch
Scene key 1
(green LED flashes after 7–12 s)
Momentary-action switch in
housing
(accessed via small opening)
Single momentary-action switch
at input T2
Scene key 1
(green LED flashes after 7–12 s)
Single momentary-action switch
at input Sc1
System points are saved for all luminaire groups together�
Saving is complete when the connected luminaires flash�
C O N F I G U R A T I O N
Action
Hold down between 7 and 12 seconds
Briefly press
Hold down between 7 and 12 seconds
Hold down between 7 and 12 seconds
Hold down between 7 and 12 seconds

Advertisement

Table of Contents
loading