Momentary-action switches on the DIMLITE control device
The DIMLITE control device has 2 or 4 inputs to which conventional momentary-action switches can be con-
nected� Briefly pressing the momentary-action switches connected to inputs T1 – T4 and T all recalls the last
value set for the luminaire groups in question or switches off the lighting� Holding down the momentary-action
switches dims or brightens the luminaire groups in question� A momentary-action switch connected to the
Sc1 input recalls lighting scene 1 or switches off the lighting� For a description of operating options, see the
section "Conventional momentary-action switches", page 10�
Note:
! Any number of momentary-action switches can be connected to an input (T1, T2, T3, T4, T all, Sc1) in parallel�
! The phase (L) adjacent to the inputs must be the same as the phase used to supply power to the DIMLITE
control device�
! Loop-through wiring of the momentary-action switches to other DIMLITE control devices is not permitted�
Inputs T1, T2, T3, T4
Example: single momentary-action switch
Beispiel: Eintastersteuerung
control
T1
T2
L
Example: single momentary-action switch control
Outputs Grp3 and Grp4 are not used.
DIMLITE 4ch
Art.-Nr. 22 161 824
Grp1
Grp2
0
min
60
0,5
1
45
30
5
T all
20
10
15
Ta: 0...50°C
T1
T2
Run-On
PIR
230/240 V AC 50/60 Hz
LUXMATE
Sc1
Lighting Management
L
Note:
! If an output is not used, the associated input (e�g� T3↓) must be electrically connected to another input
(e�g� T2↓) to which a momentary-action switch is connected� This connection method makes the switched-off
state of the unused outputs clear, which is necessary for mains disconnection, for example� In this case, the
relay contact (Rel�) only opens when all outputs are switched off�
16 DIMLITE Installation and commissioning manual 4.0 | 01.2014 | en
T3
T4
PIR
ON/OFF
Grp3
Grp4
no
funct.
Status Test
ON/Corr
Mode
T3
T4
P R O J E C T D E S I G N
Example: double momentary-action switch
Beispiel: Doppeltastersteuerung
control
T1
T2
L
Example: double momentary-action switch control
Outputs Grp3 and Grp4 are not used.
Grp1
0
min
60
0,5
45
1
only
OFF
30
5
20
10
15
T1
Run-On
L
T3
T4
Grp2
Grp3
Grp4
T2
T3
T4