Note:
! Do not use momentary-action switches fitted with integrated glow lamps, RC elements or switching thyristors
because they are not recognised by the ED-SxED input device�
! The lines between the ED-SxED input device and the momentary-action switches must not exceed 30 cm�
! The voltage supply for the ED-SxED input device is provided via the Contr�IN control line�
! Up to 8 devices (ED-Cxx, ED-SxED, ED-SENS, ED-EYE, ED-IR) can be connected to the Contr�IN control line�
! The ED-SxED input device is installed in a single recessed European socket, DIN 0606 (ø 60 mm, depth
61 mm) or a UK metal backbox (not included in supply)�
Remote control (IRTOUCH)
The IRTOUCH remote control can be used to recall three lighting scenes or switch off the lighting� It also enables
up to 4 luminaire groups to be dimmed individually� The infrared signal is received by either the ED-SENS multi-
sensor or the ED-IR infrared receiver�
Contr.IN (DA, DA)
DA DA
ED-SENS
Note:
! The range of the IRTOUCH remote control depends on the conditions in the room: the infrared signal is
influenced by surfaces that are reflective (e�g� light walls, furnishings and floors) or absorbent (e�g� dark walls)�
! Devices that emit infrared light (such as laptops, PDAs or mobile phones with active infrared interfaces, as
well as plasma screens) can also influence the infrared signal emitted by the IRTOUCH remote control�
! Only one infrared emission code from the IRTOUCH remote control can be effective for each DIMLITE system�
If you u se more than one DIMLITE system, you can operate each system separately by assigning a dedicated
infrared emission code (up to a maximum of three different infrared emission codes can be allocated for each
ED-SENS multi-sensor or ER-IR infrared receiver)� To set the IRTOUCH infrared emission code, use the multi-
switch (0-2) in the battery compartment see the section "Assigning an IRTOUCH remote control", page 30 �
P R O J E C T D E S I G N
DA DA
ED-IR
IRTOUCH
DIMLITE Installation and commissioning manual 4.0 | 01.2014 | en 15
IRTOUCH