Display
Parameter Name
Description
[r3; L o]
Output 3 Retransmit Low
[r3.Lo]
Scale
Set the low scale for the retrans-
mit output.
[r3; h i]
Output 3 Retransmit High
[r3.hi]
Scale
Set the high scale for the re-
transmit output.
[r3; C O]
Output 3 Retransmit Offset
[r3.CO]
Set the offset value for the re-
transmit output.
[hyS1]
Alarm 1 Hysteresis
[hyS1]
Set the hysteresis for an alarm.
This de- termines how far into
the safe region the input needs
to move before the alarm can be
cleared.
[Lgc1]
Alarm 1 Logic
Select the alarm output condi-
[Lgc1]
tion in the alarm state.
[LAt1]
Alarm 1 Latching
[LAt1]
Turn J on or off.
[SiL1]
Alarm 1 Silencing
[SiL1]
Turn alarm silencing on or off.
[dSP1]
Alarm 1 Message
[dSP1]
Displays an alarm message
when an alarm is active.
[hyS2]
Alarm 2 Hysteresis
[hyS2]
Set the hysteresis for an alarm.
This determines how far into
the safe region the input needs
to move before the alarm can be
cleared.
[Lgc2]
Alarm 2 Logic
[Lgc2]
Select the alarm output condi-
tion in the alarm state.
[LAt2]
Alarm 2 Latching
[LAt2]
Turn alarm latching on or off.
[SiL2]
Alarm 2 Silencing
[SiL2]
Turn alarm silencing on or off.
[dSP2]
Alarm 2 Message
[dSP2]
Displays an alarm message
when an alarm is active.
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature pa-
rameters through Modbus are in °F, by default. Writing to register 18 will toggle between °F and °C.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.
** Static set point version only (SD_C-_ _ _ _- _ _ _ _ ).
*** Profiling version only (SD_R-_ _ _ _- _ _ _ _ ).
Watl o w S eri es SD
Settings
Range
(Integer values for Modbus in
parenthesis.)
-1999.0 to 9999.0
(-1999000 to 9999000)
-1999.0 to 9999.0
(-1999000 to 9999000)
-999.0 to 999.0
(-999000 to 999000)
0.0 to 999.0
(0000 to 999000)
[AL`C] closed on alarm
(0)
[AL`O] open on alarm (1)
[nLAt] off (0)
[`LAt] on (1)
[`OFF] off (0) no silencing
[``On] on (1) silencing
[`OFF] off (0) no message
[``On] on (1) message
0.0 to 999.0 (0000 to
999000)
[AL`C] closed on alarm
(0)
[AL`O] open on alarm (1)
[nLAt] off (0)
[`LAt] on (1)
[`OFF] off (0) no silencing
[``On] on (1) silencing
[`OFF] off (0) no message
[``On] on (1)
32
Default
Modbus*
(less 40,001
offset)
Read/Write
0
*316, 317
Output 3 is a process
R/W
output (SD_ _ - _ _ _ F
- _ _ _ _ ) and [Ot`3] is
set to [rmt].
500
*318, 319
Output 3 is a process
R/W
output (SD_ _ - _ _ _ F
- _ _ _ _ ) and [Ot`3] is
set to [rmt].
0
*320, 321
Output 3 is a process
R/W
output (SD_ _ - _ _ _ F
- _ _ _ _ ) and [Ot`3] is
set to [rmt].
1.0
*106, 107
[Ot`1] is set to [dE; A L]
R/W
or [Pr; A L].
[AL`C] (0)
164 R/W
[Ot`1] is set to [dE; A L]
or [Pr; A L].
[nLAt] (0)
[Ot`1] is set to [dE; A L]
108 R/W
or [Pr; A L].
[`OFF] (0)
[Ot`1] is set to [dE; A L]
109 R/W
or [Pr; A L].
[``On] (1)
110 R/W
[Ot`1] is set to [dE; A L]
or [Pr; A L].
1.0
*121, 122
[Ot`2] is set to [dE; A L]
R/W
or [Pr; A L].
[AL`C] (0)
175 R/W
[Ot`2] is set to [dE; A L]
or [Pr; A L].
[nLAt] (0)
123 R/W
[Ot`2] is set to [dE; A L]
or [Pr; A L].
[`OFF] (0)
124 R/W
[Ot`2] is set to [dE; A L]
or [Pr; A L].
[``On] (1)
125 R/W
[Ot`2] is set to [dE;AL]
or [Pr; A L].
Appears if:
Chapt er 5 Se tup