Watlow SD Series User Manual page 31

Pid controller/pid profiling controller
Hide thumbs Also See for SD Series:
Table of Contents

Advertisement

Display
Parameter Name
Description
[PL`1]
Power Limit 1
[PL 1]
Set the maximum power output
for a control output
[PSL1]
Output Power Scale Low 1
[PSL1]
Set the low end of the range
within which the output will
scale.
[PSh1]
Output Power Scale High 1
[PSh1]
Set the high end of the range
within which the output will
scale.
[nLF1]
Output Non-linear Function 1
Select a non-linear output curve
[nLF1]
to match the response of your
system.
[AO1; U ]
Analog Output 1 Units
[AO1.U]
Set the analog output units.
[O1; L o]
Analog Output 1 Scale Low
Set the low scale for the process
[O1.Lo]
output.
[O1; h i]
Analog Output 1 Scale High
Set the high scale for the process
[O1.hi]
output
[r1; S o]
Output 1 Retransmit Source
Set the control variable that the
[r1.So]
retransmit signal represents.
[r1; l o]
Output 1 Retransmit Low
[r1.Lo]
Scale
Set the low scale for the retrans-
mit output.
[r1; h i]
Output 1 Retransmit High
[r1.hi]
Scale
Set the high scale for the re-
transmit output.
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature pa-
rameters through Modbus are in °F, by default. Writing to register 18 will toggle between °F and °C.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.
** Static set point version only (SD_C-_ _ _ _- _ _ _ _ ).
*** Profiling version only (SD_R-_ _ _ _- _ _ _ _ ).
Watl o w S eri es SD
Settings
Range
(Integer values for Modbus in
parenthesis.)
0.0 to 100.0% power (000
to 10000) (Two decimal
places implied for Mod-
bus.)
0.0 to 100.0% (000 to
10000) (Two decimal
places implied for Mod-
bus.)
0.0 to 100.0% (000 to
10000) (Two decimal
places implied for Mod-
bus.)
[`OFF] Off (0)
[Cru1] curve 1 (1)
[Cru2] curve 2 (2)
[`mA] milliamperes (0)
[uolt] volts (1)
0.00 to 20.00 mA if output
is set to mA (0000 to
20000)
0.00 to 10.00V if output
is set to volts (0000 to
10000)
0.00 to 20.00 mA if output
is set to mA (0000 to
20000)
0.00 to 10.00V if output
is set to volts (0000 to
10000)
[Proc] Process Value (0)
[~~SP] Set Point (1)
-1999.0 to 9999.0
(-1999000 to 9999000)
-1999.0 to 9999.0
(-1999000 to 9999000)
29
Default
Modbus*
(less 40,001
offset)
Read/Write
100.0%
160 R/W
[Ot`1] is set to [hEAt]
or [CooL].
0%
161 R/W
[Ot`1] is set to [hEAt]
or [CooL], [Ctr1] is set
to [`Ftb] and Output 1
is not a process output.
(not SD_ _ - _ F _ _ - _
_ _ _ )
[Ot`1] is set to [hEAt]
100%
162 R/W
or [CooL], [Ctr1] is set
to [`Ftb] and Output 1
is not a process output.
(not SD_ _ - _ F _ _ -_
_ _ _ )
[`OFF] (0)
163 R/W
[Ot`1] is set to [hEAt]
or [CooL].
[`mA] (0)
147 R/W
Output 1 is a process
output. (SD_ _ - _ F _ _
- _ _ _ _ )
4.00 mA
*148, 149
Output 1 is a process
R/W
output. (SD_ _ - _ F _ _
(mA)
- _ _ _ _ )
*152, 153
0.00V
R/W (V)
20.00 mA
*150, 151
Output 1 is a process
R/W
output. (SD_ _ - _ F _ _
10.00V
(mA)
- _ _ _ _ )
*154, 155
R/W (V)
[Proc] (0)
305 R/W
Output 1 is a process
output (SD_ _ - _ _ _ F
- _ _ _ _ ) and [Ot`1] is
set to [rmt] .
0
*306, 307
Output 1 is a process
R/W
output (SD_ _ - _ _ _ F
- _ _ _ _ ) and [Ot`1] is
set to [rmt] .
500
*308, 309
Output 1 is a process
R/W
output (SD_ _ - _ _ _ F
- _ _ _ _ ) and [Ot`1] is
set to [rmt] .
Appears if:
Chapt er 5 Se tup

Advertisement

Table of Contents
loading