Watlow SD Series User Manual page 30

Pid controller/pid profiling controller
Hide thumbs Also See for SD Series:
Table of Contents

Advertisement

Display
Parameter Name
Description
[SP; L o]
Set Point Low Limit
[SP.Lo]
Set the low range for the set
point.
[SP; h i]
Set Point High Limit
[SP.hi]
Set the high range for the set
point.
[Ftr; E ]
Input Filter
Select filtering action.
[Ftr.E]
[FLtr]
Filter Value
[FLtr]
Set the input filter value.
[Ot`1]
Output 1 Function
[Ot 1]
Set Output 1 function.
[Ctr1]
Control Method 1
[Ctr1]
Set output 1 control type. This
parameter is only used with PID
control, but can be set anytime.
[Ftb1]
Fixed Time Base 1 (Cycle
Time)
[Ftb1]
Set the time base for Fixed Time
Base Control.
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature pa-
rameters through Modbus are in °F, by default. Writing to register 18 will toggle between °F and °C.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.
** Static set point version only (SD_C-_ _ _ _- _ _ _ _ ).
*** Profiling version only (SD_R-_ _ _ _- _ _ _ _ ).
Watl o w S eri es SD
Settings
Range
(Integer values for Modbus in
parenthesis.)
Min. operating range
(of sensor) to [SP; H i] -
0.100: if {`sen} is set to
{``tc}
-328 to [SP; h i] -0.100: if
{`sen] is set to {`rtd}
-1999 to [SP; h i] -0.001: if
{`sen} is set to [`MA],
[uolt] or [`Mu]. (Set
precision with [P; d EC],
Process Decimal Places.)
[rg; L o] to max. operat-
ing range (of sensor): if
{`sen} is set to {``tc}
[SP; L o] +0.100 to 1472: if
{`sen} is set to {`rtd}
[SP; L o] +0.001 to 9999: if
{`sen} is set to [`MA],
[uolt] or [`Mu]. (Set
precision with [P; d EC],
Process Decimal Places)
[`OFF] (0) (no filtering)
[DiSP] (1) (filter only the
display value)
[CntL] (2) (filter the con-
trol input values)
[both] (3)
0.0 to 60.0 seconds (0000
to 60000)
[`OFF] Off (0)
[Pr; A L] Process Alarm (1)
[dE; ; A L] Deviation Alarm (2)
[hEAt] Heat Control (3)
[CooL] Cool Control (4)
[E; o ut] Event (5) ***
[rmt] Retransmit (6)
[`Ftb] Fixed Time Base
(0)
[Urtb] Variable Time
Base (1)
1.0 to 60.0 seconds if Out-
put 1 is a mechanical
relay (1000 to 60000)
0.1 to 60.0 seconds if Out-
put 1 is not a mechani-
cal relay (100 to 60000)
28
Default
Modbus*
(less 40,001
offset)
Read/Write
Min. op-
*240, 241
Always active.
erating
R/W
range
(thermo-
(J type):
couple)
{``tc}
*244, 245
-328:
R/W
{`rtd}
(RTD)
-999:
*248, 249
[`MA},
R/W
[uolt]
(mA, V
and
or mV)
[`Mu].
Max. op-
*242, 243
Always active.
erating
R/W
range
(thermo-
(J type):
couple)
{``tc}
1472:
*246, 247
{`rtd]
R/W
(RTD)
999:
[`MA],
*250, 251
[uolt]
R/W
and
(mA, V
[`Mu].
or mV)
[`OFF] ( 0)
89 R/W
Always active.
[Ftr; E ] is not set to
0.0
*87, 88
[`OFF].
R/W
[hEAt] (3)
143 R/W
Active only if Output 1
Always
is a process output (SD_
active.
_ - _ F _ _ - _ _ _ _)
[`Ftb] (0)
[Ot`1] is set to [hEAt]
144 R/W
or [CooL] and output
type is SD_ _-_ C _ _-_
_ _ _ or SD_ _-_ K _ _-_
_ _ _.
20.0: mech.
*145, 146
[Ot`1] is set to [hEAt]
relay
R/W
or [CooL], [Ctr1] is set
to [`Ftb] and Output 1
5.0: solid-
is not a process output.
state
(not SD_ _ - _ F _ _ - _
relay
_ _ _ )
1.0:
switched
dc
Appears if: