These categories mean, in the judgment of PB Heat, LLC: ⚠ CAUTION Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury, and minor property damage.
Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-1. Carefully read these instructions before beginning work. Understand all aspects of the installation. Contact your PB Heat sales representative or customer service for help in answering questions.
Page 5
Air Infiltration Rate Method must be used. If the building in which this appliance is to be installed b. Combining spaces on different floors: is unusually tight, PB Heat recommends that the Provide one or more permanent openings air infiltration rate be determined.
Page 6
PREINSTALLATION i. Where communicating directly or through vertical ducts with the outdoors each opening shall have a minimum free area of 1 in² per 4000 Btu/hr (22 cm² per 4000 W) of total input rating for all equipment in the space.
For new and existing installations, a Water Installation a. The required size of openings for combustion, Survey is available from PB Heat. The survey will ventilation, and dilution air shall be based on the provide information on how a hot water boiler works net free area of each opening.
PREINSTALLATION E. CIRCULATORS The Series GM™ boiler is not equipped with a circulator or a means to control circulator operation. Provide circulator and zone controls, such as Taco zoning circulator or Honeywell R845. F. PLANNING THE LAYOUT Prepare sketches and notes of the layout to minimize the possibility of interferences with new or existing equipment, piping, venting and wiring.
BOILER SET-UP 2. BOILER SET-UP 1. Provide a sound, level foundation. Locate boiler as 3. Separate the wood shipping pallet from the boiler near to the chimney or outside wall as possible and base by removing two (2) hold-down bolts at each centralized with respect to the heating system.
Design piping and size circulator(s) to suit the system. Refer to the I=B=R - Residential Hydronic Heating Installation/Design Guide and the PB Heat Water Survey for guidance. A. BOILER SUPPLY & RETURN Install boiler to protect the gas ignition system components from water (dripping, spraying, etc.) during...
130°F (54°C) entering the boiler. For more information on bypass piping, consult the PB Heat Water Installation Survey. c. If this boiler and distribution system is used in...
1. See Figures 3.6 and 3.7 for basic zoned system layouts. Circulators may be installed in either supply or return piping. Refer to PB Heat Water Installation Survey for additional information. 2. Run each zone pipe down then up to zone to prevent air accumulation in piping.
3. The glycol solution should be tested at least once a year and as recommended by the glycol manufacturer. 4. For more information, consult the PB Heat Water Installation Survey and the antifreeze manufacturer. Figure 3.8: Typical Piping with Indirect-Fired Water Heater...
VENTING 4. VENTING A. DRAFT HOOD BLOCKED VENT SWITCH ASSEMBLY 1. The boiler is equipped with a draft hood designed SHEET METAL a. provide for the ready escape of flue gases from SCREWS the boiler in the event of no draft. BLOCKED VENT b.
VENTING C. AUTOMATIC VENT DAMPER 3. Do not alter boiler draft hood or place any obstruction or non-listed damper in the vent system. INSTALLATION – GENERAL 4. Before connection of joints, inspect the vent pipe 1. Do not use one vent damper to control two or more interior for foreign objects such as tools, equipment, heating appliances.
VENTING Figure 4.4: Venting with Vent Damper in Horizontal Position F. BOILER REMOVAL FROM COMMON c. Insofar as is practical, close all building doors and windows and all doors between the space in which VENTING SYSTEM the appliances remaining connected to the common At the time of removal of an existing boiler, follow these venting system are located and other spaces of steps with each appliance remaining connected to the...
Page 17
VENTING d. Place in operation the appliance being inspected. g. Any improper operation of the common venting Follow the lighting instructions. Adjust thermostat so system should be corrected so that the installation appliance will operate continuously. conforms with the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/ Mettre en service l’appareil à...
GAS PIPING 5. GAS PIPING 1. Size and install the gas supply piping to provide 4. Connection of boiler to the gas piping system may a supply of gas sufficient to meet the maximum be made on the left side or top of the boiler. See demand of all appliances without undue loss Figure 11.1 for jacket opening locations.
Page 19
GAS PIPING 8. Disconnect the boiler and its individual shut-off valve from the gas supply piping system during any pressure testing of that system at test pressure in excess of 1/2 psig (3.5 kPa). ⚠ CAUTION Do not subject the gas valve to more than 1/2 psi pressure (3.5 kPa).
ELECTRICAL 6. ELECTRICAL This boiler is equipped with a water temperature limit control which includes a low water cutoff function and also a reset feature as described below. It is also equipped with a spark ignited intermittent ignition system. See vendor information in the boiler folder for additional information regarding the boiler controls.
ELECTRICAL B. SEQUENCE OF OPERATION, 5. Pilot flame detected. INTERMITTENT IGNITION a. Igniter off. b. Main gas on, igniting main burners. 1. Thermostat calls for heat. Note: If the pilot is not detected within 90 seconds, the 2. Limit senses boiler water temperature. Prevents igniter and pilot gas are turned off for 5 minutes.
CSD CODE REQUIREMENTS 7. CSD CODE REQUIREMENTS A. GENERAL Low Water Cut-off(s) - The Hydrolevel Hydrostat limit ® controls used on Series GM™ boilers meet ASME 1 low This section is in regard to requirements of the water cut-off requirements when used in either modular ASME CSD-1 Code, Controls and Safety Devices for of multiple boiler installations.
START-UP PROCEDURES 8. START-UP PROCEDURES A. COMPLETING THE INSTALLATION 13. Use the sequence descriptions in Section 6, paragraph B (Electrical) to follow light-off and 1. Confirm that all water, gas and electricity are shutdown sequences and to assist in diagnosing turned off.
START-UP PROCEDURES B. CONTROL DESCRIPTIONS D. CHECKING BURNER INPUT See Figure 8.5 for locations of these devices. 1. Refer to rating label mounted on the jacket top panel to obtain the rated BTU (kW) per hour input. In no 1. FLAME ROLLOUT SAFETY SHUTOFF SWITCH case shall the input to the boiler exceed the value –...
START-UP PROCEDURES Table 8.1a: Meter Conversion – Natural Gas 3. Low Water Cut-Off – Consult the manufacturer’s Burner inputs in Btu/hr for various meter timings and instructions for the low water cut-off operational heat values. (Table based on 2 cubic feet of gas through check procedure.
TROUBLESHOOTING 9. TROUBLESHOOTING ⚠ DANGER A. SHUT-DOWN CAUSED BY PILOT OUTAGE, VENT SAFETY SHUTOFF When servicing or replacing items that communicate SWITCH OR FLAME ROLLOUT SAFETY with the boiler water, be certain that: SHUTOFF SWITCH There is no pressure on the boiler. In the event of a shut-down caused by a pilot outage, The boiler is not hot.
Page 30
TROUBLESHOOTING Table 9.1: Boiler Troubleshooting Guide PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION Burners not funcitoning. 1. No power. 1. Check line voltage wiring and fuses. 2. Limit not working. 2. Check wiring and contacts, relay, temperature setting. Clean and adjust as necessary. 3.
Page 31
TROUBLESHOOTING START BEFORE TROUBLESHOOTING, NOTE: “CALL FOR HEAT” 24 VAC SUPPLY IS CONNECTED TO THE 24 V TERMINAL ON THE CONTROL. FAMILIARIZE YOURSELF WITH THE STARTUP AND CHECKOUT PROCEDURES. TURN GAS SUPPLY OFF, TURN THERMOSTAT (CONTROLLER) TO “CALL FOR HEAT.” CHECK LINE VOLTAGE POWER, LOW VOLTAGE TRANSFORMER, LIMIT CONTROLLER, THERMOSTAT (CONTROLLER), AND WIRING ALSO.
MAINTENANCE 10. MAINTENANCE ⚠ WARNING Product Safety Information Refractory Ceramic Fiber Product This appliance contains materials made from refractory ceramic fibers (RCF). Airborne RCF, when inhaled, have been classified by the International Agency for Research on Cancer (IARC), as a possible carcinogen to humans. After the RCF materials have been exposed to temperatures above 1800°F (982°C), they can change into crystalline silica, which has been classified by the IARC as carcinogenic to humans.
MAINTENANCE A. GENERAL 4. Check for water leaks in boiler and system piping. 5. Smell around the appliance area for gas. If you 1. Disconnect this boiler from the gas supply piping smell gas, follow the procedure listed in the Lighting/ during any pressure testing of the gas system.
MAINTENANCE E. ANNUALLY (BEFORE START OF HEATING h. Re-install the top of the jacket, draft hood, vent damper (if used) and vent pipe. SEASON) i. Connect blocked vent switch wiring harness to ⚠ DANGER blocked vent switch. k. Re-install burners. When servicing or replacing components, be absolutely certain that the following conditions are met:...
BOILER DIMENSIONS & RATINGS 11. BOILER DIMENSIONS & RATINGS Figure 11.1: Boiler Views Table 11.1: Series GM™ Boiler Dimensions SERIES GM™ BOILER DIMENSIONS Boiler Jacket Jacket Jacket Left of Jacket to Top of Jacket to Vent Size Model Depth Width Height C/L of Vent Vent Connector...
REPAIR PARTS 12. REPAIR PARTS Repair parts are available from your local PB Heat, LLC distributor or from Parts To Your Door at 1 (610) 916-5380 (www.partstoyourdoor.com). Note: Remember to include the boiler model number and serial number when ordering parts.
Page 37
REPAIR PARTS Figure 12.2 Table 12.2 Quantity Stock Description Required Code Gas Manifold – GM-e-05 50712 Gas Manifold – GM-e-06 50713 Gas Manifold – GM-07 50714 Gas Manifold – GM-08 50715 Main Burner – GM-e-05 50192 Main Burner – GM-e-06 50192 Main Burner –...
Need help?
Do you have a question about the Peerless Boilers GM Series and is the answer not in the manual?
Questions and answers