Oilon Junior Pro 1 J10 Operating And Maintenance Instructions Manual

Oilon Junior Pro 1 J10 Operating And Maintenance Instructions Manual

Light oil burners

Advertisement

OPERATING AND MAINTENANCE
INSTRUCTIONS FOR LIGHT OIL
Burners without preheating
Read these instructions carefully before installation, commissioning or maintenance of
the burner!
BURNERS
Junior Pro 1
J10
J18
Junior Pro 2
J20
J45
J50
Burners with preheating
Junior Pro 1
LJ10
LJ18
Junior Pro 2
LJ20
LJ45
LJ50
OILON HOME OY
P.O. Box 5, 15801 Lahti
Visiting address:
Tarmontie 4,
15860 Hollola
Tel. (03) 85 761
fax (03) 857 6239
info@oilon.com
www.oilon.com
10090943EN

Advertisement

Table of Contents
loading

Summary of Contents for Oilon Junior Pro 1 J10

  • Page 1 Junior Pro 2 LJ20 LJ45 LJ50 Read these instructions carefully before installation, commissioning or maintenance of the burner! OILON HOME OY P.O. Box 5, 15801 Lahti Visiting address: Tarmontie 4, 15860 Hollola Tel. (03) 85 761 fax (03) 857 6239 info@oilon.com...
  • Page 3: Table Of Contents

    Table of Contents Conventions in this Manual......................1 General ............................2 Burner Technical Data ........................4 3.1. Exploded View (Junior Pro 1 LJ10) ..................4 3.2. Parts List ..........................5 3.3. General ..........................7 3.4. Capacity Table ........................7 3.5. Name Plate ..........................8 Burner Installation ..........................9 4.1. Burner Mounting ........................9 4.2.
  • Page 5: Conventions In This Manual

    Conventions in this Manual Read these instructions carefully before installation, commissioning or maintenance of the burner. The given instructions must be followed. Throughout this manual, the following three symbols are used to point out very important information: WARNING! A warning alerts you to possible danger to person, if the instructions are not followed.
  • Page 6: General

    The oil supplied to the burner must be filtered before the burner oil pump. Filtration degree is from 20 - 40 μm. We recommend mounting of an Oilon Plus filter and deaerator unit. Oil atomizing pressure 800 - 1400 kPa (8 - 14 bar). Factory setting approx. 10 bar.
  • Page 7 CAUTION! The burner must be installed firmly. Vibrations may damage burner or its components. CAUTION! Disconnect the plug connector before burner maintenance or removal from the boiler. See chapter ”Connecting the Burner to the Mains”. WARNING! In case of fire or other danger: switch off the main switch close the main fuel shut-off valve outside the plant take appropriate actions.
  • Page 8: Burner Technical Data

    Burner Technical Data 3.1. Exploded View (Junior Pro 1 LJ10) 10090943EN...
  • Page 9: Parts List

    3.2. Parts List Burner housing Name plate Gasket Hinge pin Fixing screw for combustion head Combustion head J50 with adjustment ring Fixing screw for mounting flange M10 x 25 2 and/or M8 x 25 Mounting flange Flange gasket Air adjustment ring Pro 1: 1/2-opening Pro 2: 1/1-opening Fixing nut for adjustment ring...
  • Page 10 Air intake Fixing screw for air intake Clamp for run hour counter, optional extra Locking nut for grommet Grommet Fixing screw for control unit bracket Control unit bracket Signal lamp indicating readiness for operation Baseplate for control unit Fixing and earth screws for control unit Control unit Run hour counter, optional extra Fixing screw for ignition electrode holder...
  • Page 11: General

    • standard equipment for two pipe system • recommended nozzle types: - solid 45° - 60° (Junior Pro 1 J10, J18, LJ10, LJ18) - solid 60° (Junior Pro 2 J20, J45, J50, LJ20, LJ45, LJ50) • -class 2 Optional extra •...
  • Page 12: Capacity Table

    3.4. Capacity Table Burner Burner capacity range kg/h Junior Pro 1 1,4 - 2,3 17 - 27 1,7 - 2,8 20 - 33 Junior Pro 2 2,3 - 4,1 27 - 48 3,0 - 4,8 36 - 57 2,3 - 6,5 27 - 77 Junior Pro 1 LJ10...
  • Page 13: Burner Installation

    Burner Installation 4.1. Burner Mounting The furnace, which has a flame-shaped design, does not require refractory. Boilers without bottom cooling require refractory to prevent heat from reaching boiler foundations. The flame must at no point come into contact with the furnace walls. If this cannot be avoided, such points must be covered with refractory.
  • Page 14: Hinged Burner Housing

    4.2. Hinged Burner Housing As standard the burner can be hinged to both sides. 4.3. Electric Connections The burner must be connected according to the electrical diagrams delivered together with the burner. General and local standards and regulations as well as requirements of electrical equipment on electrical connections must be adhered to.
  • Page 15: Connecting The Burner To Oil Supply Line

    Filter The filter should be changed in a two-pipe system at intervals of 1 - 1,5 years. If an Oilon Plus filter and deaerator unit is used, the time of use is longer. 10090943EN...
  • Page 16: Fuel System

    2850 rpm, 5 mm²/s (cSt) 2850 rpm, 5 mm²/s (cSt) Dmax = 20 m Hmax = 4,5 m (D-H)max. = 4,5 m See the oil piping dimensions from the Oilon Plus manual, if an Oilon Plus filter and deaerator unit is used. 10090943EN...
  • Page 17: Oil Pumps

    5.2. Oil Pumps Danfoss Suntec Suction line connection Pressure regulation Return line connection By-pass plug Nozzle connection Filter Pressure gauge connection Solenoid valve coil Vacuum meter connection Oil pump venting Two-pipe system needs no venting as the air comes away when starting the burner. In order to speed up the air removal, nipple (4) in the pressure gauge connection can be loosened.
  • Page 18: Burner Operation

    Burner Operation 6.1. Operating Scheme, Oil Pump BFP 21 L3 Oil filter Ignition electrodes Return hose Solenoid valve, normally closed, NC Suction hose Nozzle Oil pump Control unit Pressure pipe Control device (thermostat/pressurestat) Burner fan Preheater, LJ-burners only Burner motor Flame detector Ignition transformer 6.2.
  • Page 19: Burner Operation Principle

    6.3. Burner Operation Principle Required input signals to control unit Control signals from control unit Limit thermostat Burner motor (fan/oil pump) Regulating thermostat Ignition transformer Preheater Solenoid valve Preheater thermostat Flame detector/flame signal Prerequisites for start-up • burner is getting fuel •...
  • Page 20 B Flame is established • flame relay (FR) is energised, whereupon terminals 8 and 3 are linked. Opening of preheater thermostat contact does not shut down the burner during flame. • burner has started • post-ignition 2 s (control from terminal 7). C Control unit/burner in normal operating condition •...
  • Page 21: Burner Adjustment

    Burner Adjustment 7.1. Capacity Regulation Adjust the burner thermal output by changing the size of the nozzle or the oil pump pressure. Combustion air quantity (and position of the adjustment ring on burner types J50 and LJ50) must be checked after having changed the nozzle. See chapter ”Change of Nozzle”. 7.1.1.
  • Page 22: 7.1.2. Oil Pump Pressure Regulation

    7.1.2. Oil Pump Pressure Regulation Fit a pressure gauge in the connection (see chapter ”Oil Pumps”). Adjust the oil pressure by turning the pressure regulating screw. The pressure increases by turning the screw clockwise and decreases counter-clockwise. Oil pump pressure is set at the factory during testing at approx.
  • Page 23: Nozzle Table

    7.2. Nozzle Table Nozzle capacities at different nozzle pressures. Calorific value 11,86 kWh/kg Density 0,833 kg/m³ Efficiency 0,9 (90 %) Capacity kW kg/h USgal/h Atomizing pressure 8 bar 10 bar 12 bar 14 bar 1,46 0,40 1,66 0,45 1,87 0,50 2,11 0,55 2,37...
  • Page 24: Nozzle And Ignition Electrode Settings

    7.3. Nozzle and Ignition Electrode Settings The measures shown are for guidance. They may vary according to the nozzle type being used. The oil spray must not come into contact with the electrodes and the diffuser disc. The electric arc should be created at that point in the oil where the spray begins. The ignition electrodes must not come into contact with diffuser disc.
  • Page 25: Adjusting The Air Velocity In The Combustion Head J50, Lj50

    7.5. Adjusting the Air Velocity in the Combustion Head J50, LJ50 Adjust the air velocity in the combustion head by turning the setting screw (5), to change the distance between the adjustment ring and the edge of the diffuser disc (4). There is a scale with four grooves in the combustion head, which is directed to the back edge of the adjustment ring according to the capacity.
  • Page 26: Adjusting The Distance And Centrality Of The Nozzle

    7.6. Adjusting the Distance and Centrality of the Nozzle Distance Loosen the locking screws (2) but not more than that the cover plate keeps contact with the burner housing. Move the cover plate in the direction of slots (see for L-measure the chapter ”Nozzle and Ignition Electrode Settings”) and tighten locking screws (2).
  • Page 27: Combustion Air Adjustment

    7.7. Combustion Air Adjustment Make sure that air, required by the burner, enters the boiler room through the fresh air ventilator. The ventilator must not be closed. The fresh air inlet must be led to the top of the room. Eventual outlet valve has to be closed in wintertime. Check, that the self-closing air flap (5) moves easy and that it is positioned according to the drawing.
  • Page 28: Flame Inspection

    7.8. Flame Inspection The ignition process may be observed through the sight glass by turning aside the cover in the shape of a drop. It must be replaced in the normal operating position after inspection. Inspection position Operation position 1 Sight glass 2 Cover 3 Fixing screw for sight glass Removal of sight glass...
  • Page 29: Control Unit Bho 64.A/Loa 24.173A27

    Control Unit BHO 64.A/LOA 24.173A27 8.1. Time Sequence Diagram (Control Program) Required input signals to control unit Control signals from control unit Legend Limit thermostat Regulating thermostat Preheater Preheater thermostat Burner motor (fan/oil pump) Ignition transformer Solenoid valve 1 Solenoid valve 2 Flame detector/flame signal Flame relay BHO 64.A...
  • Page 30: Control Functions In The Event Of Faults

    8.2. Control Functions in the Event of Faults Extraneous light / premature flame signal During pre-purge and/or pre-ignition period there must never be a flame signal. If there is a signal during this period, caused possibly by premature ignition due to a leaking oil valve, extraneous light, a short-circuit in the flame detector (photo resistor) or its wiring, a fault in the flame signal amplifier, etc., the control unit locks out on expire of the pre-purging and safety period.
  • Page 31: Measurement Of Flame Signal

    8.5. Measurement of Flame Signal WARNING! This control unit is a safety unit! Do not open it. Any unauthorized tampering can result in unforeseen detrimental consequences. 10090943EN...
  • Page 32: Maintenance

    Maintenance WARNING! Always switch off the electric power from your burner and close the manual shut-off valves in the fuel supply line before servicing your burner. When inspecting your burner you only have to switch off the electric power from your burner. The manual shut-off valves in the fuel supply line can then be open.
  • Page 33: 10. Fault Conditions And Procedures

    10. Fault Conditions and Procedures In the event of fault conditions the basic requirements for correct operation must be first examined: 1. Is the signal lamp indicating the readiness for running going on (burner switch in position ”operation”)? 2. Check, that fuse is not blown or loose. 3.
  • Page 34 CONDITION POSSIBLE CAUSE REMEDY Oil pump Supplies no oil or atomizing Dirty filter in pump Clean or replace pressure is too low Leaking suction line Seal Filter in piping is dirty Replace Pump capacity decreases: - faulty or worn pump Replace - damaged pump coupling Replace...
  • Page 35 CONDITION POSSIBLE CAUSE REMEDY Combustion head Inside oily or has heavy Distance between diffuser disc Adjust carbon deposits and nozzle incorrect Incorrect combustion air Adjust adjustment Nozzle wrong sized or of wrong Replace as appropriate type Replace Nozzle worn Other possible causes Control unit goes to lock-out Boiler smoke damper is closed Adjust Boiler or chimney is blocked...

Table of Contents