Oilon is unable to accept any liability for damage in case of: ● failure to follow these instructions ● other use than what is explained in this manual ●...
Page 6
Keep these instructions as well as the electrical diagrams available near the device. Oilon products are manufactured according to general product standards and directives, and based on our best knowledge about product design, and technologies. Operation safety is one of the leading principles in our product development. However, it is wise to be prepared, and think about safety.
Page 7
Do not use Teflon tape in piping. If burner start-up fails consecutively two times, do not restart burner before carefully investigating the reason for the failure. Do not touch hot pipes or surfaces during operation or maintenance. Emergency shutdown In an emergency, cut off power supply to the burner. Close the manual shut-off valves.
Each burner is tested separately before delivery to the customer. For more information on products, visit our web site at www.oilon.com: Oilon –> Industries –> Product material. Information on components can be found under the headline Burner parts.
Page 9
- capacity controller LCM100 and dual-fuel burner module DFM300 are mandatory to LSB bus with WD34, when using a dual-fuel burner Type plate The following illustration shows an example of the type plate of Oilon burners: M5164 1640EN 7 (95)
Type plate US ver. 1 Pos. Description Pos. Description Burner type: Degree of protection KP = Light fuel oil RP = Heavy fuel oil GP = Gas GKP = Light fuel oil and gas GRP = Heavy fuel oil and gas Overfire pressure min, IN.WC Serial number Overfire pressure max, IN.WC...
2.3 Load controller module technical data Safety equipment, do not self-service. Load controller module LCM100 Power supply 90–250 VAC Mains frequency 50–60 Hz 6 % Power consumption 18.2 VA Permissible ambient temperature -20...+60 °C -4...+140 °F LCM connector interface LCM connector interface ver. 3 Cable assembly Type Shield...
Cable assembly Type Shield Cable Cable length, m length, ft Combination input 20 mA Combination input term. 18 Analog output mA I = Input O = Output Shielded cable must always be connected to TE terminal. 2.4 Servomotor technical data Servomotor 662R5001 662R5003...
UV-cell connection ver. 2 Measuring range 0–100% Supply voltage 115 VAC –15/+10 % Min. required detector current * 35 µA Max. possible detector current * 50 µA * When supply voltage 230 V KLC connection ver. 1 Supply voltage 120 VAC -15/+10% Frequency 50 –...
Page 17
Type Dungs GMH/GML/GAO A4-4-… Degree of protection NEMA 4 Installation position Switch orientation has an effect on setting value. Standard orientation: sensing port horizontal. For other positions, refer to switch manufacturer’s documentation. Component standard UL Listed ● UL 353 ● File # MH 16628 CSA Certified ●...
Page 18
Type Siemens SKP15… Adjustment range 110–120 VAC –15/+10 % Allowed ambient and medium temperature -50 °F ... +140 °F Degree of protection NEMA 12 Closing time <0.8 s Opening time 3–6 s, depending on valve size Installation position Other positions possible except vertically upside down Component standard UL/429, FM/7400, ANSI Z21.21/CSA 6.5 C/I...
3 Installation 3.1 Space requirements Leave enough space on each side of the burner for installation, commissioning, and maintenance purposes. The minimum space requirements are presented in the following. Installation, commissioning, or service of the appliance is to be carried out by authorized and trained personnel only, adhering to all local regulations and requirements.
Page 20
The burners are attached and supported to a transportation base. The base can be lifted from all sides with a forklift. When lifting the package, the center of gravity must be in the middle between the forks to avoid falling. Lifting D047033 ver.
Do not install the burner upside down. Make sure the burner is firmly attached. 3.4 Gas valve selection table The max. capacities shown in the table are achieved when the boiler back pressure is 0. 3.5 Installing gas module to burner The gas module consists of a double solenoid valve, gas pipe, elbow fitting, and an adjustable elbow fitting.
Page 25
The assembly may vary depending on the scope of delivery. To assemble the gas module: Gas module parts are connected to each other with threaded connections. Use thread seal to seal the connections (for example Loctite 577). 1. Screw the gas inlet pipe to the mounting flange (1.1). 2.
Page 26
No tape or glue is used in this threaded connection. When dismounting the burner from the boiler, the gas line is disconnected from this connection. 5. Support the mounted gas assembly to eliminate any torsional tension. To connect the servomotor cable to the burner control unit: 1.
3.6 Installing burner to gas supply line Supply line If necessary, decrease the gas pressure with pressure regulating assembly. The gas supply line after the pressure regulator must be of the same size or one size larger than the burner’s gas pressure regulating assembly. The gas valve capacity adjustment disc must be upwards.
Page 28
● gas supply pressure ● secondary pressure ● the quantity of gas to be combusted ● type of gas If the gas inlet pressure is higher than the Pmax. value given in the burner technical data, reduce the gas inlet pressure in regulating assembly. Also, if the gas inlet pressure is not stable, stabilize the pressure with pressure regulator.
Pos. Item Pos. Item Gas pressure regulating assembly Bellows compensator/gas hose Ball valve Safety shut-off valve, if not incl. in press. regulator Gas filter Safety relief valve, if not incl. in press. regulator Pressure gauge valve Blow-off, when necessary Pressure gauge, high pressure Pressure gauge valve, when necessary Pressure regulator with safety shut-off Pressure gauge, high pressure, when...
3.9 Oil piping Oil piping manual shut-off valve The oil supply piping must be equipped with a manual shut-off valve. The flow area of the valve must correspond to the remaining oil piping. The valve must be of quickly closable type (for example, inversion 90°). It must also be easily accessible but protected from unintentional use.
Page 31
A266Y ver. 3 The maximum lengths for other viscosities can be calculated by the simple ratio of viscosities. Refer to the following tables for lengths. If the table shows lengths for 20 mm²/s (cSt) viscosity, multiply the length by 20 and divide by the value of the new viscosity mm²/s (cSt).
Overlying oil tank Underlying oil tank SUNTEC AJ4 (150 l/h) SUNTEC AJ4 (150 l/h) H (ft) ø 0.39″ ø 0.47″ ø 0.55″ ø 0.63″ H (ft) ø 0.39″ ø 0.47″ ø 0.55″ ø 0.63″ 0.43 0.94 1.81 3.15...
Page 33
Boiler equipment and remote control connections are connected to the burner wiring base. Because of the limited number of N/PE connectors and cable gland billets, possible cascade connection of the appliance must be implemented outside the burner’s wiring base. ● When using frequency converter, do cabling work and grounding according to manufacturer instructions.
4 Commissioning 4.1 First start-up Vent fuel lines before first start-up. After the first start-up check the cleanliness of the filter weekly and replace if necessary. If the filter remains clean, inspection period can be extended to one month. Pump must not operate without oil. Vent the oil pump before initial start- up and when changing the pump.
To start the burner: 1. Open the fuel shut-off valves. 2. Switch on power supply. 3. Switch on the burner from the burner control switch. To stop the burner: Turn the burner control switch to OFF position. 4.2 Adjusting nozzle and ignition electrodes Check and set the ignition electrode spark gap and the distance of the nozzle to the ignition electrodes and diffuser disc as show in the following illustration.
Burner model GKP-50 4 mm 4 mm 5 mm 0.16 inches 0.16 inches 0.20 inches GKP-90 4 mm 6 mm 7 mm 0.16 inches 0.24 inches 0.28 inches 4.3 Oil pump pressure regulation Fit a pressure gauge in the pressure gauge connection (see section Oil pump). Adjust the oil pressure by turning the pressure regulating screw.
4.5 Adjusting combustion air Adjustment ring positioning Adjustment ring position has an effect on pressure in combustion head. Adjust pressure by moving adjustment ring back and fort, thus altering the gap between adjustment ring and diffuser plate. For low capacity, adjustment ring is positioned to the front, and for high capacity to the rear.
Combustion head components A492V ver. 3 Pos. Item Flame tube Adjustment ring Diffuser disc Combustion head extension Adjustment ring locking To adjust combustion air: Combustion air volume is adjusted with adjusting cam. 1. Check the surplus oxygen level from gas flue after every adjustment with a flue gas analysator.
Page 39
Fuel Typical atomizing pressure Oil hose connection Light fuel oil 20–25 bar suction R ½” #2 fuel oil 290–261 PSI return R ½” To adjust pump pressure: ● Use the pressure adjustment screw. ● Turn the screw clockwise to increase the pressure. ●...
Do not remove the bypass plug from the oil pump. Technical data Inlet oil viscosity range: Light fuel oil 2–75 mm²/s (cSt) 2–75 mm²/s (cSt) Inlet oil maximum pressure 2 bar 29 PSI Inlet oil maximum temperature + 60 °C + 140 °F Vacuum in suction line max.
Because circumstances vary in different installation locations, the differential air pressure switch setting may have to be reset according to the current conditions to ensure burner function. Make sure not to exceed the given CO limit. Adjusting at the present nominal burner capacity 1.
The operating area of the gas pressure regulator is determined by the spring installed inside the pressure regulator. There are three types of springs and their operating areas are described in the table below. Springs can be ordered from Oilon Webshop. SKP ver. 1 40 (95)
Page 43
To change spring: 1. Remove the plug. 2. Remove the slot-head screw by turning counter-clockwise with a chisel-point screwdriver. 3. Replace the spring. Assemble in reverse order. Excessive tightening of screws may damage the component. Spring type pG (mbar) ∆p / Color Model AGA29...
The operating area of the gas pressure regulator is determined by the spring installed inside the pressure regulator. The factory setting of standard spring p is 10-30 mbar. Springs can be ordered from Oilon Webshop. To adjust outlet pressure 219598a ver. 1 1.
Page 45
To replace setting spring 219598b ver. 1 1. Remove protective cap A. Release spring by turning adjustment spindle B counterclockwise. Turn spindle to stop. 2. Unscrew complete adjustment spindle B and remove spring C. 3. Insert new spring D. 4. Assemble complete adjustment spindle and adjust desired offset. 5.
4.11 Measuring gas pressure General rules for gas pressure measurement 1. Shut off the burner. 2. Open the test point connection cover. 3. Attach a silicone hose to the test point connection. Attach a gauge to the other end of the hose. 4.
Test point 3 Test point 2 Test point 3 (mbar) (mbar) (in.Wc) (in.Wc) GKP-50 MH GKP-90 MH 13.7 4.12 Operating and display unit User interface For scrolling and changing the values, use the buttons shown on the display. Display Back...
Menu structure Menus are divided into three operating levels: ● User level (0), does not require password. ● Service level (1), password-protected for commissioning and maintenance personnel. ● Burner manufacturer level (2), password-protected. 4.13 Display menus Menu structure Menu structure ver. 4 A.
Page 49
Menu code: 0000 Fuel: OIL or GAS User level: locked (0) or open (1, 2) Upper pillar: burner capacity, % Lower pillar: flame on/off and intensity B Main menu path 0001 ver. 4 C1 Information menu path ...
Page 50
C3 service menu 3000 ver. 3 Changing the user level 1. Enter password. 2. Press Enter. To ensure safe burner operation some settings are protected by passwords that are granted to different user groups. Only authorized personnel can change these settings. Password-protected settings are: ●...
Page 51
Actuating outputs 3300 ver. 3 ● configuration of actuating outputs Ratio curve-editor 3400 ver. 3 ● editing the ratio curves Deleting ratio curves 3600 ver. 3 ● deletes all curves Setting parameters for controllers 3700 ver. 4 ● parameters for load controller module (LCM) ●...
Page 52
Changing password, service level 1 3800 ver. 3 Display settings 3900 ver. 3 ● brightness, contrast, waiting time for screen saver C4 dataset processing menu path 4000 ver. 1 Saving and restoring dataset During these actions, the burner should be shut down. To save the dataset from the burner control to the operating panel, press the saving dataset icon.
Important symbols Symbol Description Hint 6 Safety device needs replacement (250,000 burner starts). Hint 9 Boiler safety interlock chain is not closed (symbol is blinking). Hint 10 Differential air pressure information is received, although the fan is not in function (symbol is blinking).
Start-up on manual drive Check that interlocks and alarms are reset. Activate burner start-up on manual drive from the control panel’s point Pre-purge position checking Factory setting of pre-purge position is fully open (999). Resetting is possible only by PC program. Checking is automatic in every start-up sequence, because full opening is required.
Setting area: 0–999/ 90° 3400 ver. 3 For more information about adjusting combustion air, see section Adjusting combustion air. Check combustion values of ignition capacity with flue gas analysis. 4.16 Setting ignition position, oil (2-stage) The ignition position is set on the ratio control menu as the point 1 of the ratio curve (ignition position = 1-stage).
4.17 Setting ratio curve Creating curve point individually There can be a maximum of 10 curve points. Set the ratio curve in the control panel menu 3400 numbered ver. 3 Pos. Item fuel (set of curves) set condition level 2 password (burner manufacturer) menu number pillar display: capacity-% O2: residual oxygen -%...
Ignition 200, 250, 300, 400, 500, 600, 700, 800, 900, 999 On full capacity curve point: 1. Adjust the burner´s capacity. Note the ratio control. 2. Check combustion values with flue gas analysis. 3. Check flame combustion. Measure fuel consumption on every adjusting point so that the set of curves correspond to the genuine load situation.
selected curve point: ignition position X-mark indicates the active "page" I-row actual values/channel 1. Select the desired curve point page with arrow keys. 2. To enter the editing state, press Enter. 3. On the setting row, set the cursor with arrow keys to the desired point. 4.
Basic settings of a control module are carried out with DIP switches (LCM) and other settings with a PC application (LSB-remote). The DIP switches are placed on the cover of the module. In the following tables, the factory settings are underlined: DIP-1 0 = no CAN terminator 1 = CAN terminator active...
Page 60
Param. no. Description Factory setting 0065 BT300 Adjustment of the input of the firing-rate controller is used for the manual presetting of the burner firing rate BT300 2-stage valve opening point from 1-stage to 2-stage 0–999 BT300 2-stage valve closing point from 2-stage to 1-stage 0–999 BT300 Load controller module output set point, which enables...
Page 61
After changing a setting, boiler temperature or pressure should stabilize to the new value. If the values fluctuate, the parameters must be checked. Pressure and temperature should not go under or exceed the set values. Examples of typical incorrect settings: Characteristic Control process Control mode...
D-term diagram ver. 1 4.23 Load controller use The load controller functions are available on the control panel. Main menu 0000 modified ver. 1 ● measurement unit, ºC/bar ● load controller actual value, I = 105 ºC ● load controller set value, S = 100 ºC 60 (95) M5164 1640EN...
Page 63
Setting parameters for load controller 3700 ver. 4 3710 modified ver. 2 ● %-PID load controller settings ● CONST, controller type selection ● ºC/ bar, measurement unit ● 1 and 2 settings and limit settings ● PID terms ...
5 Operation 5.1 Burner operation The following illustration describes the WiseDrive system overview. System alternatives for the GKP-50 MH – 90 MH burners are described in the following sections. WD32-34 system ver. 1 The assembly may vary depending on the scope of delivery.
Page 65
See also control system manufacturer’s instructions for setting parameters. PC application The main functions of the remote PC application are: ● setting parameters, ● creating ratio curves, ● data collection, ● fault diagnostics, ● backup copying, and ● manual control. The communication between PC and the WiseDrive system is executed with LSB bus interface to USB connection.
Page 66
Servomotor and gas regulator valve D045314 ver. 1 Lamtec motor ver. 2 Servomotors drive air dampers and gas regulator valve. The servomotor, controlled by the burner control, regulates the air and fuel ratio electronically. Combustion air fan A fan attached to the burner provides sufficiently high and even air pressure for efficient combustion.
Flame detectors The burner can be equipped either with an ionization electrode or with a UV/IR detector. UV detector QRA2 for non-permanent operation UV detector KLC for non-permanent operation KLC ver. 1 QRA2 ver. 2 Ionization electrode for permanent operation UV sensor FFS 08 for permanent operation Shape of the ionization electrode can vary depending on burner type.
Page 68
A100 Control panel Control switch S1/H1 Fuel selector switch S2 (GKP) D044670 ver. 1 Control switch S1 Switch position State 0 - STOP Control voltage is cut off from burner automation and burner is shut down. 1 - CONTROL Control voltage is switched on to burner automation (burner control, servomotors).
Burner operation During burner operation, the capacity controller controls the burner control, which controls the servomotors. Servomotors adjust the gas regulator valve and air dampers between partial load and full load according to the capacity demand (modulating gas use). In oil use, the load controller module controls the burner at high-low control (2- stage).
5.5 Time sequence diagram, gas use, without ignition gas Time sequence diagram for gas US ver. 1 Closed Position Indicator X20 + X21 Flame signal POC Proof of Closure Air damper Boiler safety locking circuit Gas regulating valve Gas-firing safety locking circuit Ignition transformer Burner ON Gas valve 1 (gas side)
Page 72
Start-up ● Control unit safety features are activated. ● Fan motor starts (X25). ● Servomotors drive to the pre-purge position. 0021 ver. 2 ● The differential air pressure switch contact closes when the required air pressure is reached. If the required air pressure is not reached, a safety shutdown will be initiated.
Page 73
Follow the equivalent sequence. B – Ignition without ignition gas 0036 ver. 1 ● Preignition starts (X04). ● Safety time t9, 3s begins. ● Gas releases to nozzle. ● Gas valves 1 (X01) and 2 (X02) open (Gas valve 2 optional). ●...
Page 74
● Control unit during normal operation: the control unit adjusts the capacity controller on its modulating range to correspond to the burner load. It does this by controlling the air dampers and gas regulator. ● Control unit during manual operation: the burner operates at the capacity set by the operator.
5.7 Time sequence diagram, oil use, 2-stage Time sequence diagram for oil (two stage) ver. 1 3) Irrelevance time oil P 765 affects safety interlock chain oil and oil pressure min. when ignition valve or oil valve opens. Safety interlock chain boiler Ignition transformer Safety interlock chain burner Main oil valve and 1-stage valve...
Page 76
0021 ver. 2 ● The differential air pressure switch contact closes when the required air pressure is reached. If the required air pressure is not reached, a safety shutdown will be initiated. Control is active until a controlled shutdown. Pre-purge ...
Page 77
● Control unit during normal operation: the control unit adjusts the capacity controller with two stages. ● Control unit during manual operation: the burner operates at the capacity set by the operator. The control unit shuts down the burner if it receives a shutdown signal from boiler thermostat/pressure switch.
● Use only original spare parts. When ordering spare parts, give the burner type and serial number. This data is indicated on the burner name plate. ● In maintenance issues, contact your nearest representative or Oilon customer service. To maintain correct operation, do the following at least once a year: 1.
6.2 Dismounting combustion head and gas nozzle Combustion head structure in 50-model D046304 ver. 1 Pos. Item Pos. Item Gas nozzle Fixing screw of adjusting shaft Gas nozzle fixing screw Combustion head fixing screw (3 pcs) Locking screw of oil nozzle / ignition Combustion head body electrode holder O-ring...
Page 80
Combustion head structure in 90-model D046308 ver. 1 Pos. Item Pos. Item Gas nozzle Adjusting shaft Locking screw of gas nozzle Fixing screw of adjusting shaft Locking screw of oil nozzle/ignition Fixing screw of combustion head electrode assembly O-ring Oil nozzle/Ignition electrode assembly Locking screw of adjusting shaft ...
Check O-ring when assembling. Change if necessary. 6.3 Dismounting and changing burner motor Cut off electricity from burner and ensure the motor has no voltage. Burner control switch does not function as isolating switch to the fan motor circuit. Fan cross section D045714_US ver.
4. Screw off screws in the motor mounting flange and lift the motor away The coupling rubber remains on the pump shaft. 5. Screw off the fixing screw of the coupling frame and detach the coupling frame from the shaft end. 6.
Removing the air damper servomotor D044675 ver. 1 Pos. Item Pos. Item Locking plate fixing screw Servomotor Shaft coupling locking plate Aligning surface of servomotor’s shaft Servomotor fixing screw Shaft coupling 1. Disconnect the cables according to the instructions. 2. Loosen the shaft coupling locking plate fixing screws (shaft coupling is left attached to the air damper).
Page 84
● flame detector ● differential pressure switch ● gas pressure switches ● gas shut-off valves ● oil shut-off valves ● servomotors ● O /CO trim control (if equipped) ● Variable Speed Module (if equipped) ● boiler safety devices The burner control allows four (4) alarm resets during 15 minutes. When the limit is exceeded, fault code H889 is generated.
Page 85
Test method Outcome Boiler pre-purging begins. The burner Step 1 1. Disconnect the high pressure hose (+) from the switch. must shut down before the pre-purge 2. Start the burner. cycle is completed. After testing, reconnect the high pressure hose. Symbol ”Hint 15”...
Page 86
Gas shut-off valves If the burner is equipped with an automatic valve proving system the valves are tested to be leak free during each start-up sequence. To prove the valves manually: 1. Install a pressure gauge between the fuel shut-off valves. Refer to the valve manufacturer’s instructions for the exact location of the measuring port.
Page 87
Test method Outcome Step 1 1. Detach the hose that leads to the 1- and 2-stage capacity valves, and is lead to the drainage container. 2. Detach the main valve conductors. The burner enters lockout after pre- Step 2 Start the burner and pay attention to oil that is possibly dripping purge, because flame does not form.
Page 88
Test method Step 1 1. Detach the 1- and 2-stage capacity valve outputs and electrical terminals. If needed, mark the valves with conductors to facilitate reconnecting of them. 2. Place the drainage container under the valve outputs. Step 2 1. Detach the flame detector terminal (X20) from the control unit and install the permanent loop to the terminal according to the figure below.
Variable Speed Module (if equipped) Test method Outcome 1. Turn the control switch S1 to position 0 to switch off control During prepurge the burner stops to a voltage. fault. Fault code is H141. 2. Detach speed sensor cables from VSM100 module. 3.
6.7 Cleaning oil filter Cover Element O-ring Upper gasket Lower gasket A346A ver. 3 Make sure oil flow to the filter is cut off before starting cleaning. 1. Unscrew the cup off the cover. 2. Clean the element and the cup. 3.
Page 91
Start failure Condition Possible cause Action Burner does not start. Burner Break in control circuit. Required Find out the cause of the break. control remains in stand-by start-up signal from burner control position. terminal X10-L does not transfer to terminal X10- ↑. ...
Page 92
Motor failure Condition Possible cause Action Fan or oil pump motor does not Break in main circuit Find out cause of the break. start. Lockout occurs. Motor overload relay released Check setting, reset. Faulty motor contactor Change. Faulty motor Change.
Page 93
Flame monitoring fault, lockout Condition Possible cause Action Fan motor starts, flame forms, Incorrect flame detector position Repair. then lockout occurs. Fault code 9, Dirty flame detector Clean. Too weak flame (light) Check burner adjustments. Faulty flame detector Change.
Gas pressure switch max., fault code 609 Condition Possible cause Action Burner shuts down. Gas pressure to nozzle too high Find out cause and repair. Faulty pressure switch Change. Incorrect pressure switch setting Adjust. Oil pump Condition Possible cause Action No oil supply or too low atomizing Dirty filter...
If you need help with maintenance and service, contact your nearest representative or Oilon customer service at http://www.oilon.com/customer-service/. 6.10 Burner parts GKP-50 MH Exploded view D048897 ver. 1 The assembly may vary depending on the scope of delivery. M5164 1640EN...
Page 96
GKP-90 MH Exploded view D048844 ver. 1 The assembly may vary depending on the scope of delivery. Gas valve VGG ver. 1 94 (95) M5164 1640EN...
6.11 Burner part list Recommended change interval Part name 1–2 3–5 on demand/ year years years start-up max. Protective cover Flange gasket Fan motor Fan wheel Oil hose to nozzle valve ...