Configure Submenu
Output Voltage
Sync Freq Window
Bypass V Window
Bypass Condition
2
ECO Mode
Manual Bypass
UPS Diagnostic
Audible Alarms
EBM Number
Wiring Fault
NCL Control
Language
3
Generator Mode
Communication
Dry Relay Set
4
Converter Mode
Screen Saver
Clear Event Log
Button OFF LOCK
Charger Function
Signal Inputs
Charger Check
Reset ReplaceBAT
IP Address
Reset LoadEnergy
1
For OL1500/2200/3000RTXL2U, 100V is derated by 20%, 110/115V is derated by 10%
Output voltage default setting varies by country.
2
This function can't be set when Manual Bypass, Generator Mode or Converter Mode is enabled.
3
UPS has no bypass when Generator Mode is enabled.
4
UPS has no bypass when Converter Mode is enabled. This function can only be set before the UPS is on.
LCD SETUP FUNCTIONS
Available Settings
= [100V] [110V] [115V] [120V] [125V]
= [200V] [208V] [220V] [230V] [240V]
Range= [+/- 1%] [+/- 2%] [+/- 3%] [+/- 4%] [+/- 5%]
[+/- 6%] [+/- 7%] [+/- 8%] [+/- 9%] [+/-10%]
Range= [+10%/-10%] [+10%/-15%] [+10%/-20%]
[+15%/-10%] [+15%/-15%] [+15%/-20%]
[Check Freq/Volt] [Check Volt Only] [No Bypass]
[Disable] [Enable]
[V Range= +/-15%] [V Range= +/-10%] (for [Enable])
[Disable] [Enable]
[Battery Test] [Alarm Test] [Indicator Test] [Fan Test]
[Activate?]
[Disable] [Enable]
= [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]
[Disable] [Enable]
[Outlet On] [Outlet Off]
[English] [Español-Spanish] [Fran
[Disable] [Enable]
[Disable] [Enable]
[I/P Power Fail] [Battery Low] [Summary Alarm]
[UPS On Bypass] [UPS Fail]
[Converter Off] [O/P Freq = 50Hz] [O/P Freq = 60Hz]
[Disable] [1 Minutes] [5 Minutes]
[Activate?]
[Disable] [Enable]
[SBM] [Constant]
[Disable] [EPO] [ROO]
[Disable] [Enable]
[Activate?]
[Mode:DHCP] [Mode:Manual]
[IP Address] [Subnet Mask] [Gateway]
[Activate?]
1
ç
ais-French] [Deutsch-German]
(for [Mode:Manual])
11
Copyright © 2017 CyberPower Systems, Inc.
Default Setting
120V
208V
+/- 5%
+10%/-15%
Check Freq/Volt
Disable
V Range= +/-10%
Disable
[Battery Test]
None
Enable
0
Disable
Outlet On
English
Disable
Enable
I/P Power Fail
Converter OFF
5 minutes
None
Disable
SBM
Disable
Disable
None
Mode:DHCP
None
None