Setting Up The 9661-Etw Comms Ports - Eaton Crouse-Hinds Series Instruction Manual

Mtl intrinsically safe ethernet to serial 4 port communication module
Hide thumbs Also See for Crouse-Hinds Series:
Table of Contents

Advertisement

7
8

SETTING UP THE 9661-ETW COMMS PORTS

To change any of the settings this is done in the following step
Click on the Wi-Fi Configuration menu option, this prompts the user to
enter a username and password. The defaults are shown below, both are
case sensitive –
Username: admin
Password: Pa55w0rd
You will then see the following screen
Click on the configuration menu option and you will see the screen below
Using this page you can modify the current settings on each of the 4 Comms
ports and set them up accordingly.
The Slave offset allows the user the option of having the same serial slave
addressed devices on the 4 ports. It uses the sign and offset value to alter the
slave address received on the Ethernet before it is passed to the serial port. In
the above screen, the following configuration is used;
Port
1
2
3
4
The Modbus slave Min and Max sets the TCP slave address limits for that port.
Packet Timeout sets the maximum time waiting for the first byte of a reply
from a slave. (100ms is typical but may be extended for "slow" slaves or
reduced for "fast" ones)
TCP Slave
Offset
Addresss
1-10
+0
11-20
-10
21-30
-20
31-40
-30
Serial Slave
Address
1-10
1-10
1-10
1-10
INM 9661-ETW Rev 1