operating network equipment within the following ranges of temperature and relative
humidity (see the ASSHRAE TC9.9 "2011 Thermal Guidelines for Data Processing
Environments – Expanded Data Center Classes and Usage Guidance").
Temperature within 18° C to 27° C (64.4° F to 80.6° F)
Relative humidity less than 60%
Dew point within the range of 5.5° C to 15° C (41.9° F to 59.0° F)
Operating within this range supports the highest degree of equipment reliability, even
though the equipment data sheets may state wider ranges of minimum and maximum
temperature and humidity (for example, -40° C to 55° C and 5% to 95% RH). Continuous
equipment operation at the minimum and maximum limits is not recommended.
Keep panel sealed to avoid dust and/or animals and insects.
Inspect the installation site for moisture, loose wires or cables, and excessive dust.
Make sure that airflow is unobstructed around the device and into the air intake vents.
It is recommended weekly or every two weeks to access the web interface area of the
unit and check the equipment details in Status area. See Operation chapter for further
details regarding the equipment status.
If any abnormal conditions are observed, refer to Maintenance chapter or contact the
technical support team to obtain the suitable instructions to deal with the issue.