Installation Of Indoor; Selection Of The Best Location; Ceiling Dimension And Hanging Bolt Location - LG ABNW60GM3S1 Installation Manual

Hide thumbs Also See for ABNW60GM3S1:
Table of Contents

Advertisement

INSTALLATION OF INDOOR

6
INSTALLATION OF INDOOR

Selection of the best location

Install the air conditioner in the location that
satisfies the following conditions.
- The place shall easily bear a load exceeding
four times the indoor unit's weight.
- The place shall be able to inspect the unit as
the figure.
- The place where the unit shall be leveled.
- The place shall easily connect with the
outdoor unit.
- The place where the unit is not affected by
an electrical noise.
- The place where air circulation in the room
will be good.
- There should not be any heat source or
steam near the unit.
Top view
Unit: mm
Air inlet vents
600
Air outlet vents
Front view
Unit: mm
Inspection hole
Top view
Unit: mm
Control box
Front view
Unit: mm
Confirm the positional relationship between
the unit and suspension bolts.
- Installation the ceiling opening to clean the
filter or service under the product.
Inspection hole
600 x 600
Control box
600
1 000
Front
20 or more
(600 x 600)
Front
H
Ceiling dimension and hanging
bolt location
Install the unit above the ceiling correctly.
CASE 1
Position of suspension Bolt
- Apply a joint-canvas between the unit and
duct to absorb unnecessary vibration.
- Apply a filter Accessory at air return hole.
Ceiling Concealed Duct – Mid static
pressure
E
A
Dimension
A B C D E F G H
Capacity
(kBtu/h)
18 / 24 / 30 933.4 971.6 619.2 679 35 270 4.5 857 200 900
36 / 42
1 283.4 1 321.1 619.2 679 35 270 4.5 1 206 200 1 250
48 / 60
1 283.4 1 321.1 619.2 679 35 360 4.5 1 206 291 1 250
G
J
A
B
H
Drain hole
(Unit:mm)
I
J