Installation of Indoor, Outdoor Unit

Installation of Indoor, Outdoor Unit
Selection of the best location
Indoor unit
Install the air conditioner in the location that
satisfies the following conditions.
• The place shall easily bear a load exceeding
four times the indoor unit's weight.
• The place shall be able to inspect the unit as
the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water
drainage.(Suitable dimension "H" is necessary
to get a slope to drain as figure.)
• The place shall easily connect with the
outdoor unit.
• The place where the unit is not affected by an
electrical noise.
• The place where air circulation in the room will
be good .
• There should not be any heat source or steam
near the unit
Outdoor unit
• If an awning is built over the unit to prevent
direct sunlight or rain exposure, be careful that
heat radiation from the condenser is not
restricted.
• There should not be any animals or plants
which could be affected by hot air discharged.
• Ensure the spaces indicated by arrows from
the wall, ceiling, fence or other obstacles.
8 Ceiling Duct Type Air Conditioner
Top view
(unit: mm)
600
Front view
More than
30cm
F e
n c
o b
e o
s t a
r
c l e
s
More than
90cm
F e
n c
o b
e o
s t a
r
c l e
s
Inspection hole
(600X600)
Control box
600
Front
H
More than
30cm
More than
70cm
More than 120cm
More than
90cm
More than 90cm
More than 90cm