Installer Setting - Static Pressure Step Setting - LG ABNW60GM3S1 Installation Manual

Hide thumbs Also See for ABNW60GM3S1:
Table of Contents

Advertisement

Installer Setting - Static Pressure Step Setting

This function is applied to only duct type. Setting this in other cases will cause malfunction.
This function is only available on some products.
This is the function that static pressure of the product is divided in 11 steps for setting.
FAN
SPEED
TEMP
- Static Pressure (Code 06) setting will not be used if Static Pressure Step (Code 32) setting is
being used.
- For the static pressure value for each step, refer to the next page.
1
2
OPER
MODE
3
4
OPTIONAL OPERATION
When pressing the
button simultaneously for more than 3
seconds, the system will be entered into
the installer setting mode.
- After entering into the installer setting
mode, select the static pressure step
setting code value by pressing the
OPER
button.
MODE
* Static pressure step setting code value : 32
Select the desired setting value with the
temperature up(s), down(t) button.
00: use static pressure (code 06) set value
01~ 11: static pressure step (code 32) set value
When pressing
button, currently
established static pressure value will be set
up.
When pressing the
button simultaneously for more than 3
seconds after the setting has been
completed, the setting mode will be released.
- If there isn't any button input for more than
25 seconds, the installer setting mode will
also be released.