HOW TO SET E.S.P?
26

Installer Setting - Static Pressure Step Setting

This function is applied to only duct type. Setting this in other cases will cause malfunction.
This function is only available on some products.
This is the function that static pressure of the product is divided in 11 steps for setting.
- Static Pressure (Code 06) setting will not be used if Static Pressure Step (Code 32) setting is
being used.
- For the static pressure value for each step, refer to the next page Table. 1
When pressing the
1
button simultaneously for more than 3
seconds, the system will be entered into the
installer setting mode.
- After entering into the installer setting
mode, select the static pressure step
setting code value by pressing the
button.
* Static pressure step setting code value : 32
Select the desired setting value with the
2
temperature up( ), down( ) button.
Function Code
00: use static pressure (code 06) set value
01~ 11: static pressure step (code 32) set value
When pressing
3
established static pressure value will be set
up.
When pressing the
4
button simultaneously for more than 3
seconds after the setting has been
completed, the setting mode will be released.
- If there isn't any button input for more than
25 seconds, the installer setting mode will
also be released.
button and
Existing condition
button, currently
button and