Installation

2.1
 General Outline 
Correct  installation  of  generator  set  is  the 
precondition which ensure the normal working status 
of the generator set. The working room for generator 
set  shall  be  designed  specifically  to  meet  the 
expected functions and maintenance operations, and 
at the same time the design of generator set working 
room  shall  conform  to  local  government's  laws  and 
regulations  on  architecture,  fire  protection  laws  and 
other applicable regulations. 
2.2 
Transportation 
During  the  period  of  shipment,  protection  shall  be 
made  for  the  generator  set.  In  addition,  the 
generator  set  shall  be  tightly  secured  in  the  loading 
truck  so  that  to  avoid  any  vibration  during  shipment 
which  will  cause  the  generator  set's  components 
loosen  and  even  damaged.  During  the  process  of 
shipment  of  generator  set,  no  people  or  other 
material  is  allowed  to  place  above  the generator  set 
so  that  to  avoid  damage  to  generator  set  caused  by 
weight. 
When  loading  or  unloading  the  generator  set  to  the 
truck, forklift or hoisting device shall be used to avoid 
the generator set become tilted or fell to the ground, 
which causes damage. 
Lifting  holes  have  been  designed  on  the  common 
base  frame  of  our  generator  sets.  Some  of  the 
specifically  designed  generator  sets  has  been 
facilitated  with  lifting  holes  on  the  roof  and  forklift 
openings on the base frame etc. Users can transport 
the generator set according to the guidance specified 
on  the  specific  labels  sticked  on  the  generator  set. 
Please do not use the lifting lugs on the engine or on 
the alternator to hoist the whole generator set. 
2.3 
Design for Foundation 
The foundation which used to install and fix the diesel 
generator  set  is  very  important,  it  must  conform  to 
the following requirement: 
◆Have enough hardness and stability, so that to avoid 
deformation,  which  will  affect  the  concentricity  of 
diesel  engine  and  alternator  and  other  accessory 
parts. 
◆To support the weight of the whole generator set and 
to absorb the dynamic impact caused by unbalanced 
force and vibration during engine's running period. 
◆Generator set's foundation is not allowed to connect 
to other architecture's foundation. 
◆ The  width  and  depth  of  foundation  shall  meet 
requirement. 
◆Ensure foundation's levelness and smoothness. 
◆If possible, waste discharge sink can be sued so that 
the  waste  oil  can  be  discharged  in  a  timely  manner. 
Cable channel for generator power output cable need 
to be reserved. 
◆Normally, concrete foundation is reliable, simple and 
preferable.  When  pouring  the  concrete  foundation, 
please make sure the surface of concrete is flat, and 
no  scratch  is  allowed.  Gradienter  or  similar 
instruments  need  to  be  used  during  installation  of 
generator set and its exhaust system. 
The  design  of  foundation  can  refer  to  following 
calculation  formula:  (below  is  the  diagram  for  diesel 
generator set foundation) 
1. Generator dimension length × width: L1×W1 
2. Foundation dimension length × width: L2×W2 
    L2 =L1+400 (mm) 
    W2 =W1+400 (mm) 
3. B=2×M/ (L2×W2×D) 
    B: Thickness of foundation         
M: Generator set weight 
    L2: Length of foundation           
W2: Width of foundation 
    D: Density of Concrete (refer to 2322kg/m3) 
(Foundation drawing Refer to APPENDIX A ) 
 
2.4
 Design for Generator Set Working Room 
The installation of generator set shall be designed, so 
that  to  meet  the  demand  of  planned  operation  and 
maintenance. The complete installation shall conform 
to  local  architecture  laws,  fire  protection  laws  and 
other  applicable  regulations.  Except  the  above 
matters,  there  are  other  matters  needs  your 
attention as follows: 
◆Ensure diesel engine generator set working room is 
furnished with rainproof, sunscreen, and windproof. 
◆Ensure diesel engine generator set working room has 
good  ventilation  and  good  exhaust  system,  and  the 
area for ventilation is sufficient, and at the same time 
use  pipes  to  let  out  the  hot  air  generated  from  the 
radiator and prevent the hot air from returning. 
◆Ensure the waste gas generated during generator set 
running  period  can  be  discharged  to  outside  timely, 
and try your best to reduce the adverse effect caused 
to  environment.  The  silencer  and  exhaust  pipe  shall 
be  supported  by  the  roof,  the  supporter  shall  allow 
the  exhaust  pipe  to  expand.  It  is  not  permitted  to 
install  the  exhaust  system  directly  on  the  generator 
set. 
◆ Enough  space  shall  be  reserved  for  the  diesel 
generator  set  for  convenience  of  cooling,  operation 
and maintenance etc. Generally speaking, no foreign 
material  is  allowed  to  be  placed  within  the  area  of 