TECHCON SYSTEMS TS566R User Manual page 8

Smart controller for spray valves
Table of Contents

Advertisement

Please keep in mind that the exact pressure being fed must be indicated
correctly in this menu prior to calibrating the pressure. Not doing so may
cause the pressure display to show the incorrect pressure.
3.
Turn pressure adjustment knob counterclockwise until the wheel can no
longer be turned.
4.
Touch the 0 icon to set the pressure to 0
5.
Turn pressure adjustment knob clockwise until display output pressure is
100 psi
6.
Touch the 100 icon to set the pressure to 100
Warning: Do not turn knob all the way clockwise. 100 psi upper bound
should be set as soon as display output pressure goes from 99 to 100 psi.
Continuing to turn knob clockwise despite pressure on display already
being set at 100psi will result in incorrect output pressure readings if the
100 icon were to be pressed at that time
Note: The digital values shown at "0" and "100" icons are for reference
only. The actual calibrated values will be different
7.
Touch the Reboot icon to save the settings and reboot the system
8.
Wait until the system completes the rebooting sequence and the home
screen is displayed
The unit is now calibrated and ready to operate
8