Page 1
Domestic Pools & Spas Heat Pump Water Heater 50Hz A1 Series Technical Manual Applicable Model: (New CE safety directive) LRSJ-60/NYN1-A1 LRSJ-80/NYN1-A1 LRSJ-120/NYN1-A1 LRSJ-140/NYN1-A1 Midea reserves the right to discontinue, or change specification or designs at any time without notices and without incurring obligations.
MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual 1. Features Titanium heat-exchanger Titanium heat-exchanger has highly resistant to corrosion. High strength and durability, pressure test at water side (0.5MPa, water temperature 45° C, 60,000 times).
Page 15
Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual MCAC-HTSM-201409 LRSJ-60/NYN1-A1, LRSJ-80/NYN1-A1 LRSJ-120/NYN1-A1, LRSJ-140/NYN1-A1 Item Detail N.C. No need connect. Tout Outlet water temperature sensor. Heat-exchanger temperature sensor. Outdoor ambient temperature sensor. Inlet water temperature sensor. Temperature sensor of compressor discharge.
Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual MCAC-HTSM-201409 8. Capacity Curve LRSJ-60/NYN1-A1 Heating mode: Test condition, inlet water temperature of the units is 27° C; outlet water temperature is 29° C. Relation between heating capacity and outdoor ambient temperature:...
Page 18
MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual Cooling mode: Test condition, inlet water temperature of the units is 27° C; water volume is 2.6m Relation between cooling capacity and outdoor ambient temperature: Relation between EER and outdoor ambient temperature:...
Page 19
Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual MCAC-HTSM-201409 LRSJ-80/NYN1-A1 Test condition, inlet water temperature of the units is 27° C; outlet water temperature is 29° C. Relation between heating capacity and outdoor ambient temperature: Relation between COP and outdoor ambient temperature:...
Page 20
MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual Cooling mode: Test condition, inlet water temperature of the units is 27° C; water volume is 3.5m Relation between cooling capacity and outdoor ambient temperature: Relation between EER and outdoor ambient temperature:...
Page 21
Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual MCAC-HTSM-201409 LRSJ-120/NYN1-A1 Test condition, inlet water temperature of the units is 27° C; outlet water temperature is 29° C. Relation between heating capacity and outdoor ambient temperature: Relation between COP and outdoor ambient temperature:...
Page 22
MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual Cooling mode: Test condition, inlet water temperature of the units is 27° C; water volume is 5.0m Relation between cooling capacity and outdoor ambient temperature: Relation between EER and outdoor ambient temperature:...
Page 23
Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual MCAC-HTSM-201409 LRSJ-140/NYN1-A1 Test condition, inlet water temperature of the units is 27° C; outlet water temperature is 29° C. Relation between heating capacity and outdoor ambient temperature: Relation between COP and outdoor ambient temperature:...
MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual Cooling mode: Test condition, inlet water temperature of the units is 27° C; water volume is 5.8m Relation between cooling capacity and outdoor ambient temperature: Relation between EER and outdoor ambient temperature: 9.
MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual 1. Safety information To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring of instructions may cause harm or damage.
Page 27
Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual MCAC-HTSM-201409 Do not dispose this product as unsorted municipal waste. Collection of such waste separately for special treatment is necessary. Do not dispose of electrical appliances as unsorted municipal waste, use separate collection facilities.
MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual A discharge pipe connected to the pressure-relief is to be installed in a continuously downward direction and in a frost-free environment. The maximum target temperature is limited to 35° C in order to protect the swimming pool liner.
Page 29
Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual MCAC-HTSM-201409 2.1 Unit outlook 2.2 Carrying of unit Decide the correct way of conveying the equipment. Try to transport the unit with orginal package. Please put down the unit as gentle as possible during removing, unit could be leaned no more than 45 degree.
Page 30
MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual The installation as well as electric and hydraulic connections must be carried out in compliance with applicable standards. Keep the unit out of reach of children. 2.4 Distance of unit ground screws (Unit: mm)
Page 31
Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual MCAC-HTSM-201409 2.6 Water pipe connection of the unit Water pipe joint specifications Name Connective pipe PVC Φ50 Outlet water pipe PVC Φ50 Inlet water pipe PVC Φ25 Drainage connecting pipe ...
Page 32
MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual /h – pressure drop 0.22bar. Average water flow 5.5m Installation diagram V1, V2, V3: By-pass valve; V4, V5: Regulator valve (Recommended facilitating adjustment close to the machine.
Page 33
Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual MCAC-HTSM-201409 All wiring should be finished, before power is switched on to the unit, please confirm all connections are correct. Select the power supply and wire size according to this manual. The size of the power cable of the unit should be greater than that of ordinary motors.
MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual deconcentrator and connected to the power supply device. Please select the wire diameter by following methods: The diameter of main wire is conducted by the horsepower of the HPWH and preceding table.
Page 35
Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual MCAC-HTSM-201409 In case of the unit requiring deicing during heating operation, to prevent the heating efficiency from decreasing, defrosting operation will turn on automatically (Approx. 2~10min). In the process of defrosting operation, the unit air supply motor will stop running.
Page 36
MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual Disoperation occurs during unit working: In case disoperation caused by lighting or vehicle radio, cut off the manual power switch, and turn it on again, afterward press RUN/STOP key.
Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual MCAC-HTSM-201409 After leave the unit idle for a long period, please check the followings: Inspect the air intake orifice or air outlet is blocked periodically. If any , remove the foreign substance to let the air flow fluently.
Page 38
MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual 4.2 Name and function description of LCD screen of wired controller 1. COOL indicator: When user sets the cooling water mode, it lights up. 2. HEAT indicator: When user sets the heating water mode, it lights up.
Page 39
Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual MCAC-HTSM-201409 will go out automatically except POOL TEMP indicator lighting. When the unit is running, if there is no operation or malfunction for 10s, the backlight of the display will go out automatically. After 30s, all indicator will disappear except operation mode and pool temperature.
MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual Power on and power off Press ON/OFF button, and after all the above have finished, the system will run as the setting. Just simply press the same button to stop it.
Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual MCAC-HTSM-201409 In the process of trial run, please check the following items: 口 Check whether the switch of the wired controller is normal. 口 Check whether the functional keys of the controller are normal.
Page 42
MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual In case of following malfunction, please cut off the manual power switch, and repair it. The fuse was burnt out frequently or the earth leakage protective device was broken up frequently.
Page 43
Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual MCAC-HTSM-201409 Error code and protection code: Code Explanation Solution Check whether the communication wire is damaged. Check whether the communication wire is correctly connected Outdoor unit and to the motherboard.
Page 44
MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual Continues Code Explanation Solution Check whether the Tp temperature sensor is damaged. Discharge pipe Check whether the Tp temperature sensor is correctly temperature sensor connected to the motherboard. Tp error.
Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual MCAC-HTSM-201409 7. Resistance characteristic of temperature sensor Resistance characteristic of ambient Temp., pipe Temp. and suction Temp. sensor. Temp. Resistance Temp. Resistance Temp. Resistance Temp. Resistance value (kΩ) value (kΩ) value (kΩ)
Page 46
MCAC-HTSM-201409 Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual Resistance characteristic of discharge temperature sensor Temp. Resistance Temp. Resistance Temp. Resistance Temp. Resistance value (kΩ) value (kΩ) value (kΩ) value (kΩ) (° C) (° C) (° C) (°...
Need help?
Do you have a question about the LRSJ-60/NYN1-A1 and is the answer not in the manual?
Questions and answers
Wat betekent P9 storing