Patterson-Kelley P-K STORM ST-5000 Installation & Owner's Manual page 23

Gas fired boiler w/ nuro™ control system natural gas
Hide thumbs Also See for P-K STORM ST-5000:
Table of Contents

Advertisement

As per ANSI Z21.13b * CSA 4.9b:
The use of cellular core PVC, cellular core CPVC, or Radel
prohibited.
The use of external insulation on plastic vent pipe is prohibited.
Acceptable Venting Materials
Model
Country AL29-4C 316L SS PVC CPVC
ST-2500 US
Yes
ST-3000 US
Yes
ST-3500 US
Yes
ST-4000 US
Yes
ST-5000 US
Yes
ST-6000 US
Yes
ST-2500 Canada
Yes
ST-3000 Canada
Yes
ST-3500 Canada
Yes
ST-4000 Canada
Yes
ST-5000 Canada
Yes
ST-6000 Canada
Yes
NOTE 1: When this material is used for venting, it must be listed to ULC-S636.
NOTE 2: When this material is used for venting, it must be listed to either UL-
1738 or ULC-S636 (depending on the local requirements). Consult the local
boiler codes for more information.
Revised: December 8, 2021
Released: December 8, 2021
Yes
No
Yes
Yes
No
Yes
Yes
No
Yes
Yes
No
Yes
Yes
No
Yes
Yes
No
Yes
Yes
No
Note 1
Yes
No
Note 1
Yes
No
Note 1
Yes
No
Note 1
Yes
No
Note 1
Yes
No
Note 1
 Patterson-Kelley 2021
All Rights Reserved.
P-K Storm
Technical Service 1.877.728.5351
®
as venting materials is
POLYPROPYLENE
Note 2
Note 2
Note 2
Note 2
Note 2
Note 2
Note 1
Note 1
Note 1
Note 1
Note 1
Note 1
2691000273 P-K Storm ST2500-ST6000
Installation and Owners Manual Rev C.docx
TM
Gas Fired Boiler
Page 12