AC-DC Power Supplies Enclosed type Instruction Manual Terminal Block UAW-10 Function UAW-10 UAW-10 Input voltage range UAW-10 Inrush current limiting UAW-10 Overcurrent protection UAW-11 Overvoltage protection UAW-11 Output voltage adjustment range UAW-11 Remote ON/OFF UAW-11 Remote sensing UAW-11 Isolation UAW-12 Thermal protection Series Operation and Parallel Operation UAW-12...
Instruction Manual AC-DC Power Supplies Enclosed type 1 Terminal Block 2 Function lUAW125S 2.1 Input voltage range The range is from AC85V to AC132V/AC170V to AC264V which is automatically selected internally. But after the input voltage is applied, avoid changing AC100V/AC200V. AC input voltage must have a range from AC85V to AC132V/AC170V AC(N) to AC264V for normal operation.
Instruction Manual AC-DC Power Supplies Enclosed type 2.4 Overvoltage protection 2.7 Remote sensing The overvoltage protection circuit is built-in and comes into effect (1)When not using remote sensing function at 115 - 140% of the rated voltage (except 3V output voltage type: it operates at 4.00 - 5.25V).
Instruction Manual AC-DC Power Supplies Enclosed type lUAW250S UAW500S 2.9 Thermal protection lUAW250S UAW500S Parallel operation is available by connecting the units as shown below. n Thermal protection is built-in. If this function comes into effect, As variance of output current drew from each power supply is shut down the output, eliminate all possible causes of overheat- maximum 10%, the total output current must not exceed the ing, and drop the temperature to normal level.
Page 6
Instruction Manual AC-DC Power Supplies Enclosed type n In parallel operation, please connect diode to the + side of the out- 4.2 Derating put circuit. If diode is connected to the-side, it will damage the The operative ambient temperature is different by with/without unit or/and the balancing function will not work.
Instruction Manual AC-DC Power Supplies Enclosed type nWhen fan is set separately, the temperature of part A of the unit UAW250S should be below 75 degree by flowing cooling-air inside of the unit. Keep the temperature of part A and B as below. part A (chassis of power supply) : below 90 part B (C13)