O P E R A T I N G I N S T R U C T I O N S
ReLy LOOP1
Safety relay

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ReLy LOOP1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SICK ReLy LOOP1

  • Page 1 O P E R A T I N G I N S T R U C T I O N S ReLy LOOP1 Safety relay...
  • Page 2 Original document This document is an original document of SICK AG. O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK Subject to change without notice...
  • Page 3: Table Of Contents

    Disassembly....................Module exchange..................Electrical installation................ 18 Device connection..................8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 4 List of figures..................36 List of tables..................37 O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK Subject to change without notice...
  • Page 5: About This Document

    8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 6: Additional Information

    Ö The LED is flashing. O The LED is illuminated continuously. O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK Subject to change without notice...
  • Page 7: Safety Information

    At altitudes of over 4,000 m above sea level • In explosion-hazardous areas 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 8: Requirements For The Qualification Of Personnel

    O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK...
  • Page 9: Product Description

    2 application diagnostic outputs (not safe) • 1 Test output (not safe) 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 10: Compatible Sensor Types

    Further topics • "Status indicator (LED)", page 26 O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK Subject to change without notice...
  • Page 11: Project Planning

    Sufficient distance must be kept for the connected cables before the module (front side). 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 12: Electrical Integration

    Application diagnostic output Y1 is based on the push-pull principle, meaning it can both absorb and apply current. O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK...
  • Page 13: Restart Interlock

    (contactors) have dropped out when the device is switched on. Further topics • "Device connection", page 18 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 14: Connection Diagrams

    6, page O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK Subject to change without notice...
  • Page 15: Mounting

    Figure 5: Mounting Attach module to mounting rail. 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 16: Disassembly

    Figure 7: Dismantle front connector O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK Subject to change without notice...
  • Page 17: Mount The Front Connector

    The front connector engages with an audible click. 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 18: Electrical Installation

    The ground connection of all connected devices must have the same potential as O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK...
  • Page 19: Terminals On Front Connector

    Use without restart interlock, without external device monitoring (EDM): Connect U and S1 with a wire jumper. 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 20 Further topics • "Connection diagrams", page 14 O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK Subject to change without notice...
  • Page 21: Configuration

    Set the DIP switch for the desired reset option to position 1. 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 22: Configuring Flexi Loop Reset

    Approach Set the DIP switch for the desired monitoring option to position 1. O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK...
  • Page 23: Activating Configuration

    ✓ The PWR LED flashes red (1 Hz). 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 24: Commissioning

    The thorough checks must be carried out by qualified safety personnel or specially qualified and authorized personnel, and must be documented in a traceable manner. O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK...
  • Page 25: Troubleshooting

    Additional information on troubleshooting can be found at the responsible SICK subsid‐ iary. 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 26: Status Indicator (Led)

    O Green Complementary information • "Configuration", page 21 O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK Subject to change without notice...
  • Page 27: Decommissioning

    SICK will be glad to help you dispose of these devices on request. 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 28: Technical Data

    Fine wire (1×) 0.14 mm … 1.5 mm O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK Subject to change without notice...
  • Page 29 ≤ 100 m Cable resistance ≤ 10 Ω 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 30 –25 °C … +55 °C (UL/CSA: surrounding air temperature) O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK Subject to change without notice...
  • Page 31: Switch-Off Delay Without Continuous Arcing

    Figure 11: Switch-off delay without continuous arcing Inductive load L/R 40 ms Resistive load 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 32: Dimensional Drawings

    20,1 87,7 85,5 78,7 Figure 13: Dimensional drawing O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK Subject to change without notice...
  • Page 33: Internal Circuitry

    TECHNICAL DATA 11.3 Internal circuitry Figure 14: Internal circuitry 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 34: Ordering Information

    ReLy LOOP1 Flexi Loop safe series RLY3-LOOP100 1100696 connection O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK Subject to change without notice...
  • Page 35: Annex

    (part number: see the type label entry in the “Ident. no.” field). 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 36: List Of Figures

    13. Dimensional drawing....................32 14. Internal circuitry......................33 O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK Subject to change without notice...
  • Page 37: List Of Tables

    12. Electrical data - enabling current paths (13, 14, 23, 24, 33, 34)......30 13. Ambient data.......................30 14. Ordering information....................34 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 38 LIST OF TABLES O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 8024311/2021-07-30 | SICK Subject to change without notice...
  • Page 39 LIST OF TABLES 8024311/2021-07-30 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy LOOP1 Subject to change without notice...
  • Page 40 E-Mail office@sick.com.gr E-Mail info@sick.ru Vietnam Hong Kong Singapore Phone +65 6744 3732 Phone +852 2153 6300 Phone +65 6744 3732 E-Mail sales.gsg@sick.com E-Mail ghk@sick.com.hk E-Mail sales.gsg@sick.com Detailed addresses and further locations at www.sick.com SICK AG | Waldkirch | Germany | www.sick.com...