As shown in Figure2-2, the firewall provides a primary grounding point at the rear panel and an
auxiliary grounding point at the left side. The primary grounding point has a grounding sign and a
grounding screw.
The grounding screw at the primary grounding point is also applicable to the auxiliary grounding
point. To use the auxiliary grounding point, attach the grounding cable to the grounding point before
you install the firewall in a rack.
The procedure is the same for connecting a grounding cable to the primary grounding point and the
auxiliary grounding point. This section uses the primary grounding point as an example.
To connect the grounding cable:
1.
Remove the grounding screw from the primary grounding point at the device rear.
2.
Attach the grounding screw to the ring terminal of the grounding cable.
3.
Use a screwdriver to fasten the grounding screw into the grounding hole.
4.
Connect the other end of the grounding cable to the grounding strip on the rack.
Figure2-2 Grounding the firewall by using the primary grounding point

Installing the firewall in a standard 19-inch rack

WARNING!
To avoid bodily injury and device damage, at least two persons are required to install the firewall.
CAUTION:
• Ensure a clearance of 1 RU (44.45 mm, or 1.75 in) between the firewall and walls or other
devices for heat dissipation.
• The mounting brackets and chassis rails are required to support the weight of the chassis.
To mount the firewall in a rack, make sure the rack meets the requirements described in Table2-1.
Table2-2 Firewall dimensions and rack requirements
Firewall dimensions
Height—88.1 mm (3.47 in)
Width—440 mm (17.32 in)
Total depth—775.5 mm (30.53 in)
660 mm (25.98 in) for the chassis
90 mm (3.54 in) for the cable
Primary grounding point
Auxiliary grounding point
Rack requirements
A minimum of 1 m (3.28 ft) in depth
(recommended).
A minimum of 100 mm (3.94 in) between the front
rack posts and the front door.
A minimum of 760 mm (29.92 in) between the
front rack posts to the rear door.