Address
0xF000
0xF001
0xF100
0xF200
0xF201
0xF202
0xF300
0xF301
0xF302
0xF303
0xF304
0xF305
0xF306
0xF400
0xF401
0xF402
0xF403
0xF404
0xF405
Wieland Electric GmbH | BA000917 | 08/2021 (Rev. C)
Access
Description
-/W
Samples stores period [min]
-/W
Allowed
• bit 0 – active level on input BIN1
• bit 1 – active level on input BIN2
• bit 2 – active level on input BIN3
• bit 3 – active level on input BIN4
• bit 4 – analogy input AN1 lower limit overrun
• bit 5 – analogy input AN1 upper limit overrun
• bit 6 – analogy input AN2 lower limit overrun
• bit 7 – analogy input AN2 upper limit overrun
• bit 8 – limit frequency CNT1 overrun
• bit 9 – limit frequency CNT2 overrun
-/W
Binary inputs negative logical
• bit 0 – input BIN1
• bit 1 – input BIN2
• bit 2 – input BIN3
• bit 3 – input BIN4
-/W
Binary outputs normal level
• Bit 0 – output OUT1
-/W
Feeder – impulse number on input BIN1/CNT1
-/W
Feeder – impulse length on output OUT1 [1/8 sec]
-/W
AN1 – samples period [sec]
-/W
AN1 – multiplicative constant (with sign)
-/W
AN1 – additive constant (with sign)
-/W
AN1 – hysteresis value (with sign)
-/W
AN1 – lower limit (with sign)
-/W
AN1 – upper limit (with sign)
-/W
bits 7–3:
AN1 – metering circuit switch time
• 0 → 1/64 s
• 1 → 2/64 s
• ...
• 30 → 31/64 s
bits 2-0:
AN1 – samples number for average
• 0 → 1 sample
• 1 → 2 samples
• 2 → 4 samples
• 4 → 8 samples
5 → 16 samples
-/W
AN2 – samples period [sec]
-/W
AN2 – multiplicative constant (with sign)
-/W
AN2 – additive constant (with sign)
-/W
AN2 – hysteresis value (with sign)
-/W
AN2 – lower limit (with sign)
-/W
AN2 – upper limit (with sign)
CNT expansion port