Gasboy TopKAT Installation Manual page 55

Fuel management system
Table of Contents

Advertisement

Wiring Diagrams
• Conductor: 18 AWG stranded wire. Number of conductors to be determined by pulser
• Shield: Foil-wrapped 100% coverage and/or tinned copper braid 90% coverage
• Drain Wire: Stranded, tinned copper, 20 AWG or larger/or braided shield
• Voltage Rating: Maximum operating voltage of 600 VDC
• Environmental: Gas- and oil-resistant; suitable for wet or dry locations.
Gasboy can supply Belden 1063A (P/N C09655) which is a UL-Listed, 4-conductor cable that
meets the requirements listed above.
Note: Belden 1063A is UL-Listed but not CSA listed.
MDE-4319A TopKAT Fuel Managment System Installation Manual · November 2005
Mechanical Interface Option
Page 43

Advertisement

Table of Contents
loading

Table of Contents