6
|
Installation
To connect the drain piping to the indoor unit
Installer and user reference guide
32
1~1.5 m
a Hanging bar
O Allowed
X Not allowed
▪
Rising piping. If necessary to make the slope possible, you can install rising
piping.
-
Drain hose inclination: 0~75 mm to avoid stress on the piping and to avoid air
bubbles.
-
Rising piping: ≤300 mm from the unit, ≤675 mm perpendicular to the unit.
a
b
a Metal clamp (accessory)
b Drain hose (accessory)
c Rising drain piping (vinyl pipe of 25 mm nominal diameter and 32 mm outer
diameter) (field supply)
d Hanging bars (field supply)
▪
Condensation. Take measures against condensation. Insulate the complete drain
piping in the building.
▪
Combining drain pipes. You can combine drain pipes. Make sure to use drain
pipes and T-joints with a correct gauge for the operating capacity of the units.
a T-joint
NOTICE
Incorrect connection of the drain hose might cause leaks, and damage the
installation space and surroundings.
1 Push the drain hose as far as possible over the drain pipe connection.
2 Tighten the metal clamp until the screw head is less than 4 mm from the
metal clamp part.
3 Check for water leaks (see
4 Install the insulation piece (drain pipe).
a
≤300
1000~1500
a
b
c
d
d
a
"To check for water
(mm)
(mm)
4
leaks" [
33]).
FCAHG71~140HVEB
Split system air conditioners
4P561449-1B – 2021.07