comfort and a slightly greater output. Comfort
mode prioritises the temperature comfort, the
control system only accepts a smaller deviation
from the set room temperature.
In Eco mode the heating adapts to the desired
level a little more slowly, when a temperature
change occurs, which gives lower energy
consumption (only valid for units with internal
temperature sensor).
Open door setp. diff.
Set by how much the set point value (Room temp.
day/night) is to increase when the door is open.
>Installer menu>Heating
settings
Eco / Comfort
Open door setp. diff.
Heating step diff.
Factory setting
Set point value difference open door: 3.0 K (0 K –
-10 K)
Heating step diff.
The temperature difference between connection
of the electrical heating step.
>Installer menu>Heating
settings
Open door setp. diff.
Heating step diff.
Heating step limit
Factory setting
Heating step diff: 1.0 K (0 K – 10 K)
Heating step limit
Possibility of limiting the heating.
>Installer menu>Heating
settings
Heating step diff.
Heating step limit
Sensor calibration
Factory setting
Heating step limit: 2/3 (1-2/3)
SIRe Advanced Air Curtains Electric
>Installer menu>Heating
settings
Open door setp. diff.
3.0 K
>Installer menu>Heating
settings
Heating step diff.
1.0 K
>Installer menu>Heating
settings
Heating step limit
3
Sensor calibration
If the sensor displays the wrong values these can
be calibrated. Some display errors may occur,
but this is primarily due to the location (cold/hot
surfaces etc). The value + or – adds to or subtracts
from the measured value (for example +2K gives
an increase of the displayed value of 2 degrees).
>Installer menu>Heating
settings
Heating step limit
Sensor calibration
Stepless heat control
Factory setting
Room temperature sensor: 0.0 K (-10 K – 10 K)
Outdoor temperature sensor: 0.0 K (-10 K – 10 K)
Stepless heat control
For stepless control of electrical heating, for
example via external triac.
>Installer menu>Heating
settings
Sensor calibration
Stepless heat control
Control range limit
Factory setting
Stepless heat control: ON (Off - not selectable)
Control range limit
The maximum room temperature that a user can
select is limited to between 5 – 35°C.
>Installer menu>Heating
settings
Sensor calibration
Stepless heat control
Control range limit
Factory setting
Control range limit temperature: 35°C (5 –
35°C)
GB
>Installer menu>Heating
settings>Sensor calibration
Room temp. sensor
Outdoor temp. sensor
>Installer menu>Heating
settings>Sensor calibration
Room temp. sensor
0.0 K
>Installer menu>Heating
settings
Stepless heat control
3
>Installer menu>Heating
settings
Control range limit
35°C
35