DVC6200 Digital Valve Controllers
August 2015
Figure 40. CSA Loop Schematics—FIELDVUE DVC6200f and DVC6200p
CSA APPROVED
ENTITY DEVICE
1 NOTE 7
GE42818 Sheet 3, Rev. F
CSA APPROVED
FISCO TERMINATOR
GE42818 Sheet 4, Rev. F
1 SEE NOTES IN FIGURE 42
48
CLASS I, ZONE 0, GROUP IIC
CLASS I, DIV 1, GROUPS ABCD
CLASS II, DIV 1, GROUPS EFG
T CODE
T (amb)
CLASS III
T4
≤ 80_C
T5
≤ 77_C
T6
≤ 62_C
NOTE 1, 3 1
ENTITY FIELDBUS LOOP
T CODE
T (amb)
T4
≤ 80_C
T5
≤ 77_C
T6
≤ 62_C
CSA APPROVED
FISCO DEVICE
NOTE 2, 3 1
HAZARDOUS LOCATION
DVC6200F, DVC6200FS
DVC6200P, DVC6200PS
Vmax = 24 VDC
Imax = 380 mA
Ci = 5 nF
Li = 0 mH
Pi = 1.4 W
HAZARDOUS LOCATION
CLASS I, ZONE 0, GROUP IIC
CLASS I, DIV 1, GROUPS ABCD
CLASS II, DIV 1, GROUPS EFG
CLASS III
DVC6200F, DVC6200FS
DVC6200P, DVC6200PS
Vmax = 17.5 VDC
Imax = 380 mA
Ci = 5 nF
Li = 0 mH
Pi = 5.32 W
FISCO LOOP
Quick Start Guide
NON‐HAZARDOUS LOCATION
CSA APPROVED
BARRIER
1 NOTE 1, 3, 4, 5, 6
NON‐HAZARDOUS LOCATION
CSA APPROVED
FISCO BARRIER
1 NOTE 2, 3, 4, 5, 6