WEIGHTRAC 31 • Four-wire 4 ... 20 mA/HART
Fig. 6: Mounting the crossbeam
1
Screws M10 x 40 (12 pcs.)
2
Wedge lock washer M10 Nordlock (24 pieces)
3
Crossbeam (1 piece)
4
Toe clamps (4 pieces)
5
Nut M10 (12 pieces)
6
Support stand (2 pieces)
2. Place the four clamping claws (4) with the corrugation downwards
into the crossbeam (3).
3. Insert the screws (1) with one wedge lock washer (2) through the
clamping claws (4).
4. Place a wedge lock washer (2) from below on each screw (1) and
screw one nut (5) onto each screw.
5. Align the crossbeam (3) with the upper holding fixtures of the
support stands (6) and tighten the nuts (5) evenly with 45 Nm
(33.2 lb ft).
Mounting - Support stand
1. Place the premounted measuring frame above the conveyor belt
and determine a suitable position for mounting the support stands
(6).
Mount the measuring frame as well centered as possible and
at an angle of 90° above the conveyor belt. Keep enough lateral
distance to the conveyor belt.
4 Mounting
1
2
3
4
2
5
6
17