Emerson Dixell IEV12D Installing And Operating Instructions page 45

Table of Contents

Advertisement

LoP
Minimum
operating
pressure
HSH
Maximum
super heating
value
LSH
Minimum
super heating
value
1592026270 IEV12-14D GB r.1.0 21.02.2019
Evaporation
Automatic action of the controller to
pressure < LOP
counteract the LoP;
activation
Active alarm relay output if enabled
threshold
by parameter;
delayed by Et39
Enable the buzzer;
seconds
icon flashes;
Code of alarm on the display.
Super heating
Automatic action of the controller to
value > High
counteract the HSH;
superheating
Active alarm relay output if enabled
threshold Et12 /
by parameter;
Et32 delayed by
Enable the buzzer;
Et41 seconds
icon flashes;
Code of alarm on the display.
Super heating
Automatic action of the controller to
value < Low
counteract the LSH;
superheating
Active alarm relay output if enabled
threshold Et13 /
by parameter;
Et33 delayed by
Enable the buzzer;
Et42 seconds
icon flashes;
Code of alarm on the display.
IEV
Automatic.
The condition to
come out from
minimum
operating
pressure are:
- the equivalent
temperature of
the pressure
probe exceeds
Et17/Et37 +
4.0°C
- Et17 <
Evaporation
pressure
converted to
temperature <
Et17+4°C and
superheating <
Et13 (low
superheating set
point)
After LOP alarm
reset, the driver
carries out the
aperture of the
valve by
Et16/Et36 steps
at each second
of operation
Automatic when
the superheating
is less or equal
to Et12/Et32 –
1.0°C
Automatic when
the superheating
temperature is
higher or equal
to Et13/Et33 +
1.0°
46/56