Step 3: Connect to I-2533T-FD module
Press the "Refresh" button to scan and list all the necessary
I-2533T-FD modules on "Module Name" location. Then select the
necessary I-2533T-FD module and press "Connect" button to start
to connect with it.
Step 4: Configure user-defined CAN/CAN FD baud rate
1. User can set the CAN port operation mode and user-defied
CAN baudrate parameters on the "CAN Port Settings" frame.
All settings will take effect after reboot the module.
[CAN Mode]
"CAN FD" :
"Non-ISO":
[User-defined CAN Baud Rate Settings]
"Arbitration":
"Data Phase":
Set the CAN port into CAN FD mode. When setting
the CAN port into CAN FD mode, the CAN port can
process CAN/CAN FD messages, otherwise this
port just can process CAN messages.
Non-ISO operation. If this parameter is checked,
the module uses the CAN FD frame format as
specified by the Bosch CAN FD Specification V1.0.
Otherwise, CAN FD frame format will follow
according to ISO11898-1.
CAN/CAN FD arbitration phase bit rate. Valid
range: 10 kbps ~ 1000 kbps.
CAN FD data phase bit rate. Valid range: 100 kbps
~ 10000 kbps