Humidity Too High When Unit Is Not Running; Humidity Too High When Unit Is Running And Cooling; Other Miscellaneous Problems; Unit Operates But The Power Switch Light Is Not On - Wine Guardian D088V Installation, Operation And Maintenance Manual

Ducted and ducted vertica wine cellar cooling systems
Table of Contents

Advertisement

Humidity too high when unit is not running

Possible Cause
Unit needs to run to dehumidify

Humidity too high when unit is running and cooling

Possible Cause
Too much moisture in cellar

Other Miscellaneous Problems

Unit operates but the power switch light is not ON

Possible Cause
Bulb is burned out

Unit is leaking water

Possible Cause
Piping from unit to drain is trapped
Trap plugged
Condensate pan plugged
Unit not level

Unit is running properly, but the sound of the unit is objectionable

Possible Cause

Noise is from airflow

Noise if from unit
64
Solution
Run unit. Seal openings around doors (gasket
and sweep)
Solution
Poor vapor barrier installation
Humidifier malfunction refer to the humidifier
instructions.
Add dehumidifier to surrounding space
Solution
Replace bulb
Solution
Re-pipe to remove external traps
Clean trap
Remove blockage and clean
Level with shims
Solution

Redirect airflow

Add baffles
Add insulated ductwork
Add sound baffle between unit and occupied
Part No. 15H0127-00