Defrost cut in
temperature
Defrost cut out
temperature.
Compressor run time
setting for defrost.
Room sensor
calibration
46
Setting 12
Press "Settings" button to advance to Setting
12.
Press the "Up" or "Down" arrow buttons to
adjust to the desired setpoint
This setting will be adjustable from 25 Deg F
to 40 Deg F (4 Deg C - 5 Deg C). Default
will be 35 Deg F (2 Deg C).
There must be at least a 1 Deg F/C difference
between defrost cut in and cut out set points.
Setting 13
Press "Settings" button to advance to Setting
13.
Press the "Up" or "Down" arrow buttons to
adjust to the desired setpoint.
This setting will be adjustable from 35 Deg F
to 50 Deg F (2 Deg C - 10 Deg C). Default
will be 40 Deg F (5 Deg C).
There must be a least a 1 Deg F/C difference
between defrost cut in and cut out set points.
Note: This setpoint must be 1 Deg F/C higher
than setting 12.
Note: If C is selected and then switched back
to F the default cut out will change to 41 Deg
F.
Setting 14
Press "Settings" button to advance to Setting
14.
Press the "Up" or "Down" arrow buttons to
adjust to the desired setpoint.
The setting for compressor run time can be
adjustable from 1 to 12 hours in 1 hour
increments. Default will be 1 hour.
Setting 15
Press "Settings" button to advance to Setting
15.
Press the "Up" or "Down" buttons to adjust to
the desired set point. Maximum setting is +5
Deg F, minimum setting is -5 Deg F (-15 Deg
C) . Factory default is zero (0). Sensor
calibration setpoint changes the actual display
reading (temperature only) by the value of
this setting.
Example: Sensor reading = 55 Deg F (13
Deg C)
Setting 15 set to +4
Display reading = 59 Deg F (15 Deg C)
Part No. 15H0127-00