Section 2: General Information

Specifications

Description
Max. cont. grid-tied AC power @ 122°F (50°C)
Max. cont. islanded AC power @ 104°F (40°C)
with single 6 module battery cabinet
Max. cont. islanded AC power @ 104°F (40°C)
with 2 battery cabinets (8 modules minimum)
Max. cont. Islanded AC power @ 122°F (50°C)
Peak motor starting current (2 sec)
Normal output frequency AC
Grid Voltage Line to Neutral (L-N)
Grid Voltage Line to Line (L-L)
Peak efficiency
CEC weighted efficiency
AC terminals wire size
DC terminals wire size
STOP terminals wire size
Weight
Thermal management
Weatherization rating
Enclosure Material
Description
REbus voltage
REbus current
REbus Input short circuit current
REbus Input source backfeed current to input source
Output power factor rating AC
Operating voltage range AC, XVT076A03 (L-N)
Operating voltage range AC, XVT076A03 (L-L)
Operating voltage range AC, XVT114G03 (L-N)
Operating output voltage range AC, XVT114G03 (L-L)
Continuous output current AC grid-tied
PCS controlled current grid-tied
Continuous output current AC islanded
Output fault current duration
Full Power operating ambient temperature range
Utility interconnection voltage and frequency trip limits and
trip times
Trip voltage and frequency limits
Trip voltage accuracy
Trip time accuracy
1
Peak Performance
2
Inverter limits its REbus current to adhere to its AC power rating. Total REbus current capability from multiple REbus sources
may safely exceed this value as the inverter safely limits the amount utilized.
3
Rating for one DC input. Four total.
4
Includes ambient temperature rising from inverter operation.
* In Island mode XVT114G03 Protected loads only supply 2 phases 120 VAC L-N, 208 L-L which results in lower power than in grid
tied 3 phase mode.The low value of the range is for full L-L loading while high value of the range is full L-N loading.
Owner's Manual for Generac PWRcell Inverter
Units
kW
kW
1
kW
kW
A rms
Hz
VAC
VAC
%
%
AWG
AWG
AWG
lb (kg)
-
-
-
3
4
XVT076A03
7.6
9.0
11.0
8.8
240
96
96.5
powder-coated steel
Units
Min
V dc
360
A dc
A dc
A dc
-
V rms
108
V rms
216
V rms
108
V rms
184
A rms
Arms
A rms
A / ms
°F (°C)
-4 (-20)
See Voltage and Frequency Trip Thresholds in PWRcell Inverter
Installation Manual for more information.
%
General Information
XVT114G03
11.4
9.0
Range 9.6 to 11.0*
Range 7.5 to 8.8*
50
60
120
208
97
96.5
14 to 6
18 to 6
28 to 16
62.7 (28.4)
forced convection
NEMA Type 3R
Nominal
380
120
240
120
208
50 / 200
+122 (+50)
2% +/- 2 cycles
Max
420
2
30
30
30
1
130
260
130
228
32
32
42
5