Outdoor Distribution (14.4 kV and 25 kV)
Installation of Arc-Resistant Models

Table of Contents

Section
Qualified Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Read this Instruction Sheet . . . . . . . . . . . . . . . . . . . . . . . 2
Retain this Instruction Sheet . . . . . . . . . . . . . . . . . . . . . . 2
Proper Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Understanding Safety-Alert Messages . . . . . . . . . . . . . . 4
Following Safety Instructions . . . . . . . . . . . . . . . . . . . . . 4
Replacement Instructions and Labels . . . . . . . . . . . . . . . 4
Packing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
June 22, 2009 © S&C Electric Company
Page
Section
Access to Interior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cable Terminations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Fault Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Completing the Installation . . . . . . . . . . . . . . . . . . . . . 14
Dielectric Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Instruction Sheet 665-506
Page
5
1

Advertisement

Table of Contents
loading

Summary of Contents for S&C PME Pad-Mounted Gear

  • Page 1: Table Of Contents

    S&C Manual PME Pad-Mounted Gear Outdoor Distribution (14.4 kV and 25 kV) Installation of Arc-Resistant Models Table of Contents Section Page Section Page Introduction Installation Qualified Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Access to Interior .
  • Page 2: Introduction

    S&C Manual PME Pad-Mounted Gear . Familiarize yourself with “Safety Information” on page 4 . Retain this This instruction sheet is a permanent part of your S&C Manual PME Pad-Mounted Gear . Instruction Sheet These instructions should be stored in the low-voltage connection enclosure, using the instruction manual holder .
  • Page 3: Warranty

    The standard warranty contained in seller’s standard con ditions of sale (as set forth in Price Sheet 150) does not apply to S&C Manual PME Pad-Mounted Gear where fuse units, fuse-unit end fittings, holders, refill units, or switch blades of other than S&C manufacture are used in con junction with S&C SME Mountings .
  • Page 4: Safety Information

    Safety Information Understanding There are several types of safety-alert messages which may appear throughout this Safety-Alert Messages instruction sheet as well as on labels attached to the S&C Manual PME Pad-Mounted Gear . Familiarize yourself with these types of messages and the importance of the various signal words, as explained below .
  • Page 5: Inspection And Handling

    Inspection and Handling Packing S&C Manual PME Pad-Mounted Gear is fastened to a wood skid for shipment . Any components specified, such as fuses, refill units, fuse holders, end fittings, etc ., are packed separately and, insofar as practicable, are shipped within the enclosure .
  • Page 6: Installation

    Installation Access to Interior Step 1 TO OPEN DOORS: Access to the interior of S&C Pad-Mounted Gear is controlled by the S&C Penta-Latch® Mechanism, which must be opened with a pentahead socket wrench or tool except when hexhead actuators (Catalog Number Suffix “-B1” or “-B2”) are specified .
  • Page 7 Installation TO CLOSE DOORS: Close the left-hand door, where applicable, and secure it with the latch by rotating the latch downward over the stop on the outer edge of the door . See Figure 3 . The right-hand door of double-door models of pad-mounted gear is equipped with the Penta-Latch Mechanism which latches automatically when the door is closed .
  • Page 8: Placement

    Installation Placement Step 2 At the installation site, remove all separately packaged components shipped within the pad-mounted gear enclosure, including the steel deflectors . Two-compartment models are furnished with two large deflectors; four-compartment models are furnished with four large deflectors and two small deflectors . Set these items aside in a protected area .
  • Page 9 Installation If excess lengths of direct-buried cable are to be fed into the termination compartments as the unit is lowered, special attention must be paid to the cable position in the fuse termination compartments. Open the doors and secure them with the door holders, to allow the cable to be fed over the door stiles .
  • Page 10 Installation After mounting the enclosure to the mounting pad, the deflectors are to be assembled to the unit . First, bolt one of the large deflectors to the bottom of a switch or fuse compart- ment frame using the supplied B\zn-inch serrated nuts . Refer to Figures 6, 7, and 8 . Repeat for the other compartment(s) .
  • Page 11 Installation On four-compartment models, install the two small deflectors . Refer to Figure 9 . Each small deflector is installed behind the two large deflectors . Then bolt the small deflector into place using the supplied B\zn-inch serrated nuts . Confirm that the complete deflector assembly installation matches Figure 7 on page 10 .
  • Page 12: Cable Terminations

    Installation Cable Terminations Step 3 Ç DANGER Before energizing the gear, replace the shipping caps on all bushings and bushing wells with elbows or insulated protective covers or plugs . Failure to replace the shipping caps can result in a flashover and serious personal injury or death. Switch terminals are equipped with 600-ampere-rated bushings, and fuse terminals are equipped with 200ampere-rated bushing wells .
  • Page 13: Fault Indicators

    Do not allow solvents used to clean cables prior to termination to contact the viewing windows . The solvent can permanently etch the polycarbonate material. The 600-ampere bushings supplied in S&C Manual PME Pad-Mounted Gear are equipped with a stud as standard . Bushings are available without studs (Catalog Number Suffix “-M1”) to accommodate 600-ampere elbows that do not require a stud .
  • Page 14: Completing The Installation

    Installation Completing the Step 6 Check functional operation of key interlocks, if furnished . Installation Ç WARNING An extra set of keys is provided with pad-mounted gear that has optional key interlocks . These keys are for use only during installation . After installation, either: (1) de stroy the extra set of keys or (2) make them accessible only to authorized persons .
  • Page 15: Dielectric Testing

    Dielectric Testing For the convenience of users who normally perform elec trical tests on system components such as pad-mounted gear, appropriate withstand test values are given in the table below: RATINGS AND INSULATION TEST VALUES Voltage Rating, kV Test Voltage Withstand, kV Impulse (BIL) 60-Hertz, RMS 14 .4...
  • Page 16: Specifications

    Specifications OPTIONAL FEATURES Suffix to be Added to Item Pad-Mounted Gear Catalog Number Light Gray Outdoor Ultradur® Finish instead of Olive Green With Olive Green Outdoor Ultradur Finish -A10 Stainless-Steel Enclosure With Light Gray Outdoor Ultradur Finish -A12 For use except when option suffix “-F2” is specified -B1a Hexhead Actuator for use in lieu of pentahead actuator on all Penta-Latch Mechanisms...