5 Electrical Connection
Note!
Tools
Connecting
the Soliphant to the
separate housing
Fig. 23
Connecting wires between
the separate housing and
Soliphant, connection in the
Soliphant housing
24

5.2 Connection on site

Note:
• All national regulations concerning installation are to be observed!
• All national regulations concerning explosion protection are to be observed if the
Soliphant is to be mounted in an explosion hazardous area.
• Usual tools for connecting measuring instruments.
• Cover lock: Allen key for Allen screws 0.12 in ~
• Dummy plugs for cable entries: key for Allen screws
35
and 0.55 in ~
/
" (14 AF)
64
• Flexible metallic protective tubing for connecting cable: open-end spanner 1
(27 AF)
• Protect the Soliphant housing from dripping water
Unscrew the housing cover of the Soliphant
Do not wipe away the lubrication from around the thread of the cover or the gasket!
• Place the cover on a clean surface only.
• Unscrew the protective packing (yellow plastic plug) from the cable entry
• Insert the connecting cable in the pipe or in the flexible metallic protective tubing
and make watertight according to national regulations
• Connect the 6 wires of the connecting cable to the terminal block according to their
colour coding
• Connect the green/yellow protective earth to the ground connection in the Soliphant
housing
If the connecting cable is to be shortened:
– Free wires to a length of approx. 4 in (approx. 100 mm)
– Strip the insulation of the wires 0.2 in (5 mm) and attach end sleeves
– Strip the insulation of the green/yellow protective earth 0.4 in (10 mm) and attach
end sleeves
– Remove the screen braiding cleanly and insulate
• Screw down the housing cover of the Soliphant
Soliphant
housing
YE WH BU BN BK
GNYE
FTM 30 DR, FTM 31 DR, FTM 32 DR
1
/
" (3 AF)
8
YE
= yellow
RD
WH
= white
BU
= blue
BN
= brown
BK
= black
RD
= red
GNYE = green/yellow
—>